beautypg.com

Electrical data – Burkert Type 8611 User Manual

Page 12

background image

12

TechnicalData

6.4.2. rating plate of the control cabinet

model

8611 Panel 24VDC

00210206

W16LU

Prozessregler

S/N xxxxxx

Assembly model

- Panel (control cabinet

Controller type

Power supply voltage
Controller design

Serial number

Manufacturer's code

Order part number

Example:

Fig. 4: Example: Rating plate of the control cabinet model

6.5.

electrical data

Operating voltage:

24 V DC ±10 %,
filtered and controlled

Power consumption

without load: approx. 2 W
with load: maximum 48 W
100 % ED: 36 W

Controller sampling rate:

300 Hz

6.5.1. inputs

set-point value

Standard 4 - 20 mA

Input impedance: 70 Ω
Resolution:

5.5 µA

Standard 0 - 10 V

Input impedance: 11.5 kΩ
Resolution:

2,5 mV

sensors

Standard 4 - 20 mA

Input impedance: 70 Ω
Resolution:

5.5 µA

Frequecy

Input 1 External sensor

Frequency range: min. 0.25 Hz / max. 1 kHz
Input resistance: > 1 kΩ
Signal types:

Sine, rectangle, triangle
(> 3000 mVss, max. 30 Vss)

Input 2 Internal Hall sensor

Frequency range: min. 0.25 Hz / max. 1 kHz

(only in conjunction with Bürkert
flow-rate fitting Type S030)

Pt 100

(2-wire) Measuring range:

0 °C ... 200 °C

Measured current:

1 mA

Measuring error:

< 0.5 °C

english

Type 8611