beautypg.com

Burkert Type 2100 User Manual

Page 8

background image

8

Technical data

Minimum pilot pressure: flow direction below the seat
(medium flow against the closing direction of the valve)
Required minimum pilot pressure P

min

with control function A:

Actuator size

[mm]

50

70

90

130

≤ DN 50

130

DN 65

P

min

[bar]

5.2

4.8

5.0

5.0

5.6

Tab. 3: Required minimum pilot pressure - CF A

The required minimum pilot pressure P

min

with control function B and

I (flow direction below the seat) is dependent on the pressure of the
medium

5)

.

Minimum pilot pressure: flow direction above the seat
(medium flow with the closing direction of the valve)
The required minimum pilot pressure P

min

with control function A

(flow direction above the seat) is dependent on the pressure of the
medium

5)

.

5)

The pressure diagrams are in the operating instructions on the
Internet:

www.burkert.com

6.5. General technical data

Media

Control medium

Neutral gases, air

Flow media

Water, alcohol, fuel, hydraulic liquids,
saline solutions, lye, organic solvents

Materials and
connections

see data sheet or operating instructions

Installation

as required, preferably with actuator in
upright position.

Protection class

IP67 in accordance with IEC 529 /
EN 60529

6.6. Control functions (CF)

A

1(P)

2(A)

Normally closed by spring action.

B

1(P)

2(B)

Normally open by spring action.

I

1(P)

2(A)

Actuating function via reciprocal pressurization.

Tab. 4: Control functions

english

Type 2100