Start-up

Control functions A and B:

Connect the control medium to the pilot air port 1 of the actuator
(see “Fig. 6”).

Silencer
For the versions with a plug-in connection the silencer for reducing
the exhaust air noise is supplied loose.

Plug the silencer into the free air discharge connection 2 (see
“Fig. 6”).

If used in an aggressive environment, we recommend con-
veying all free pneumatic connections into a neutral atmo-
sphere with the aid of a pneumatic hose.

Control function I:

Connect the control medium to the pilot air port 1 and 2 of the
actuator (see “Fig. 6”)
Pressure on connection 1 opens the valve.
Pressure on connection 2 closes the valve.

1

2

Pilot air port

CFA, CFB, CFI

Air discharge connection

CFA, CFB

Pilot air port CFI

Fig. 6:

Pneumatic connection

Control air hose:
6/4 mm or 1/4“ control air hoses can be used.
Optionally a pilot air port is possible via a G 1/8 thread.

8. START-UP

8.1. Safety instructions

WARNING!

Risk of injury from improper operation!
Improper operation may result in injuries as well as damage to the
device and the area around it.
• Before start-up, ensure that the operating personnel are familiar

with and completely understand the contents of the operating

instructions.

• Observe the safety instructions and intended use.
• Only adequately trained personnel may operate the equipment/

the device.

8.2. Pilot pressure

WARNING!

For control function I – Danger if pilot pressure fails!
For control function I control and resetting occur pneumatically. If
the pressure fails, no defined position is reached.
• To ensure a controlled restart, first pressurize the device with

pilot pressure, then switch on the medium..

Set the pilot pressure according to the type label specifications,
chapter “6. Technical data” and flow direction (chapter “8.3.
Flow direction”).