beautypg.com

Alpha Technologies FXM350_Micro350 UPS User Manual

Page 61

background image

59

017-241-B0 Rev B

Programmable Dry Contact Time of Day Action
You can assign a dedicated timer to a dry contact. Upon entering the Inverter operating mode, the timer

is activated and begins to count down from a user defined value. When the timer reaches zero, the pro-

grammed dry contact relay is activated (Status = ON).

Inverter

mode

entered

Dry contact

activates when timer

counts down to zero

Timer

starts to

count down

Microprocessor

Figure 41 — Programmable Timer Operation

An example of a typical application of this timer-controlled dry contact function is control of a traffic light.

When the grid power fails, the Alpha FXM goes into the Inverter mode and continues supplying backup pow-

er to the traffic light. Since the batteries supplying the backup power have limited capacity, a timer controlled

dry contact is usually configured to switch the traffic light into the flashing amber or flashing red mode after a

user-defined period to conserve battery power.
This setup works for non-rush hour traffic, but during rush hour, it may be desirable to keep the traffic light

running normally as long as backup power is available. To address this issue, a new feature called the Time 

of Day Action

has been added to deactivate the timer during a user defined time period up to twice each

day.

Inverter

mode

entered

Dry contact activates

when enabled timer

counts down to zero

Timer starts to

count down

if enabled

Microprocessor

Real time clock

Peak period

settings

Disable Timer (Action=ON) or

Enable Timer (Action=OFF)

Figure 42 — Time Of Day Action Operation