Programmable Dry Contact Time of Day Action
You can assign a dedicated timer to a dry contact. Upon entering the Inverter operating mode, the timer
is activated and begins to count down from a user defined value. When the timer reaches zero, the pro-
grammed dry contact relay is activated (Status = ON).
Inverter
mode
entered
Dry contact
activates when timer
counts down to zero
Timer
starts to
count down
Microprocessor
Figure 41 — Programmable Timer Operation
An example of a typical application of this timer-controlled dry contact function is control of a traffic light.
When the grid power fails, the Alpha FXM goes into the Inverter mode and continues supplying backup pow-
er to the traffic light. Since the batteries supplying the backup power have limited capacity, a timer controlled
dry contact is usually configured to switch the traffic light into the flashing amber or flashing red mode after a
user-defined period to conserve battery power.
This setup works for non-rush hour traffic, but during rush hour, it may be desirable to keep the traffic light
running normally as long as backup power is available. To address this issue, a new feature called the Time
of Day Action
has been added to deactivate the timer during a user defined time period up to twice each
day.
Inverter
mode
entered
Dry contact activates
when enabled timer
counts down to zero
Timer starts to
count down
if enabled
Microprocessor
Real time clock
Peak period
settings
Disable Timer (Action=ON) or
Enable Timer (Action=OFF)
Figure 42 — Time Of Day Action Operation