Next use the down arrow to proceed to the next section.
If this is the first time the Genie has run, the Genie will guide the user through the setup of
the motor parameters. If the Genie has run previously, the user can choose the desired
Setup Selection to configure a specific function in the controller. Use the up and down
arrows to highlight the desired setup and press [OK] to enter the setup. The choices for
the Setup Selection menu are described in the table below.
Table 17: Setups with the Genie
Setup
Description
Motor
This setup allows configuration of the motor parameters.
These settings are found on the motor nameplate.
Application
The Application setup allows the user to configure the
motor type, operating mode, units and ramps.
Feedback
This setup allows configuration of up to 3 feedback
sources. The feedbacks can be taken in to the controller
through analog inputs or communications.
Setpoint
This setup allows configuration of up to 2 setpoints. If
multiple setpoints are used, the setpoint is selected by
using DI 33.
Constant Slave
This setup configures the controller to operate up to 2
external fixed speed pumps using the 2 on board relays.
Flow Compensation
This setup configures the Flow Compensation function
which can automatically adjust the system setpoint to
offset the affect of friction loss in the system.
Pump Protection
This setup configures Sleep Mode, Flow Check, No Water/
Loss of Prime and Pump Protect functions.
Digital Input
This setup allows configuration of the digital inputs.
Relay and Analog Output
This setup allows configuration of the relay and analog
outputs.
Communication
This setup configures the on board fieldbus
communications.
Copy to LCP
This setup allows all the controller parameters to be
copied to the LCP. This is helpful for saving the drive state
or to quickly configure another controller with the same
settings.
Copy from LCP
This setup allows all the controller parameters to be
copied from the LCP. This is helpful for reverting the drive
to a previous state or to quickly configure another
controller with the same settings.
Motor setup
The motor data required to complete the Motor Setup can be found on the motor
nameplate. The Start-Up Genie will prompt the user for Motor Power (HP), Motor Nominal
Voltage, Motor Nominal Frequency (Hz), Motor Nominal Speed (RPM), Motor Current
(FLA), Motor Service Factor (%) and Motor Type. If the Motor Service Factor indicated on
the motor nameplate is 1.15 enter 115% for Motor Service Factor. Be sure to properly set