Resolution for analog inputs
10 bit (+ sign)
Accuracy of analog inputs
Maximum error 0.5% of full scale
Bandwidth
20 Hz/100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-
voltage terminals.
1
2
3
4
5
9
10
11
7
6
8
1.
+24 V
2.
18
3.
37
4.
Functional isolation
5.
RS485
6.
Control
7.
PELV isolation
8.
High voltage
9.
Mains
10. Motor
11. DC-Bus
Figure 42: PELV isolation
Pulse
Programmable pulse
2/1
Terminal number pulse
29
1)
, 33
2)
/ 33
3)
Maximum frequency at terminal 29, 33
110 kHZ (push-pull driven)
Maximum frequency at terminal 29, 33
5 kHZ (open collector)
Minimum frequency at terminal 29, 33
4 Hz
Voltage level
See Digital Inputs in the General Technical Data section.
Maximum voltage on input
28 V DC
Input resistance, Ri
Approximately 4kΩ
Pulse input accuracy (0.1–1 kHZ)
Maximum error: 0.1% of full scale
Encoder input accuracy (1–11 kHZ)
Maximum error: 0.05% of full scale
The pulse and encoder inputs (terminals 29, 32, 33) are galvanically isolated from the
supply voltage (PELV) and other high-voltage terminals.
1)
only
2)
Pulse inputs are 29 and 33
Analog output
Number of programmable analog outputs
1
Terminal number
42
Current range at analog output
0/4–20 mA
Maximum load GND — analog output
500 Ω
Accuracy on analog output
Maximum error: 0.5% of full scale
Resolution on analog output
12 bit
Technical Specification