Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual
Page 131

Starting torque (variable torque)
maximum 110% for 60 s
1)
Overload torque (variable torque)
maximum 110% for 60 s
Torque rise time in VVC
plus
(independent of fsw)
10 ms
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the
torque step from 0 to reference is 4–5 x torque rise time.
Cable lengths and cross sections for control cables
1)
Maximum motor cable length, screened
150 m
Maximum motor cable length, unscreened
300 m
Maximum cross-section to control terminals, flexible/
rigid wire without cable end-sleeves
1.5 mm
2
/16 AWG
Maximum cross-section to control terminals, flexible wire
with cable end-sleeves
1 mm
2
/18 AWG
Maximum cross-section to control terminals, flexible wire
with cable end-sleeves with collar
0.5 mm
2
/20 AWG
Maximum cross section to control terminals
0.25 mm
2
/24 AWG
1)
For power cables, see Power Dependent Specifications.
Digital inputs
Programmable digital inputs
4 (6)
1)
Terminal number
18, 19, 27
1)
, 29
1)
, 32, 33
Logic
PNP or NPN
Voltage level
0–24 V DC
Voltage level, logic ‘0’ PNP
<5 V DC
Voltage level l, logic ‘1’ PNP
>10 V DC
Voltage level, logic ‘0’ NPN
2)
>19 V DC
Voltage level, logic ‘1’ NPN
2)
<14 V DC
Maximum voltage on input
28 V DC
Pulse frequency range
0–110 kHZ
(Duty cycle) Min. pulse width
4.5 ms
Input resistance, Ri
Approximately 4 kΩ
Analog inputs
Number of analog inputs
2
Terminal number
53, 54
Modes
Voltage or current
Mode select
Switch S201 and switch S202
Voltage mode
Switch S201/switch S202 = OFF (U)
Voltage level
—10 to +10 V (scaleable)
Input resistance Ri
Approximately 10 kΩ
Maximum voltage
±20 V
Current mode
Switch S201/switch S202 = ON (I)
Current level
0/4 to 20 mA (scaleable)
Input resistance Ri
Approximately 200Ω
Maximum current
30 mA
Technical Specification
Aquavar
®
Intelligent Pump Controller INSTRUCTION MANUAL