Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual
Page 139

Recommended maximum fuse
[HP]
Type RK1
Type RK1
Type RK1
Type J
15–20
5014006-040
KLSR045
A6K-35R
HSJ35
25
5014006-050
KLS-R50
A6K-45R
HSJ45
30
5014006-050
KLS-R50
A6K-50
HSJ50
40
5014006-063
KLSR060
A6K-60R
HSJ60
50
5014006-080
KLSR075
A6K-80R
HSJ80
60
5014006-100
KLSR100
A6K-100R
HSJ100
75
2028220-125
KLS-124
A6K-125R
HSJ125
100
2028220-150
KLS-150
A6K-150R
HSJ150
125
2028220-200
KLS-175
A6K-175R
HSJ175
Table 45: 525-690 V, Frame Sizes B and C
Recommended maximum fuse*
[HP]
Maximum
prefuse
Bussmann
E52273
RK1/JDDZ
Bussmann
E4273 J/JDDZ
Bussmann
E4273 T/JDDZ
SIBA E180276
RK1/JDDZ
LittelFuse
E81895
RK1/JDDZ
Ferraz-
Shawmut
E163276/
E2137
RK1/JDDZ
Ferraz-
Shawmut
E2137 J/HSJ
15
30 A
KTS-R-30
JKS-30
JKJS-30
5017906-030
KLS-R-030
A6K-30-R
HST-30
20–25
45 A
KTS-R-45
JKS-45
JJS-45
5014006-050
KLS-R-045
A6K-45-R
HST-45
30
60 A
KTS-R-60
JKS-60
JJS-60
5014006-063
KLS-R-060
A6K-60-R
HST-60
40
80 A
KTS-R-80
JKS-80
JJS-80
5014006-080
KLS-R-075
A6K-80-R
HST-80
50
90 A
KTS-R-90
JKS-90
JJS-90
5014006-100
KLS-R-090
A6K-90-R
HST-90
60
100 A
KTS-R-100
JKS-100
JJS-100
5014006-100
KLS-R-100
A6K-100-R
HST-100
75
125 A
KTS-R-125
JKS-R-125
JJS-125
2028220-125
KLS-150
A6K-125-R
HST-125
100
150 A
KTS-R-150
JKS-150
JJS-150
2028220-150
KLS-175
A6K-150-R
HST-150
* UL compliance 525-600 C only
Substitute fuses for 240 V
Table 46: Substitute fuses
Original fuse
Manufacturer
Substitute fuse
KTN
Bussmann
KTS
FWX
Bussmann
FWH
KLNR
Littel Fuse
KLSR
L50S
Littel Fuse
L50S
A2KR
Ferraz-Shawmut
A6KR
A25X
Ferraz-Shawmut
A50X
Connection tightening torques
Table 47: Tightening of terminals
Power (HP)
Torque (Nm)
Enclosure 208–230 V 380–460 V
575 V
525–600 V
Mains
Motor
DC
connection
Brake
Earth
Relay
A2
1.5–3
1.5–5
1.8
1.8
1.8
1.8
3
0.6
Technical Specification