Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual
Page 125

Frequency type designation
0075
0100
0150
0200
0250
Maximum input current
Continuous (3 x 200–240 V) [A]
22.0
28.0
42.0
54.0
68.0
Intermittent (3 x 200–240 V) [A]
24.2
30.8
46.2
59.4
74.8
Additional specifications
Estimated power loss at rated maximum load [W]
4)
269
310
447
602
737
IP20 maximum cable cross section (mains, brake, motor, and load
sharing)
10, 10 (8,8–)
35,-,- (2,-,-)
35 (2)
50 (1)
IP21, IP55, IP66 maximum cable cross section (mains, motor) [mm
2
/
AWG]
10, 10 (8, 8–)
35, 25, 25
(2, 4, 4)
50 (1)
IP21, IP55, IP66 maximum cable cross-section (brake, load sharing)
[mm
2
/AWG]
16, 10, 16 (6, 8, 6)
35,-,- (2,-,-)
50 (1)
Weight enclosure IP20 [kg]
12
12
12
23.5
23.5
Weight enclosure IP21 [kg]
23
23
23
27
45
Weight enclosure IP55 [kg]
23
23
23
27
45
Weight enclosure IP66 [kg]
23
23
23
27
45
Efficiency
3)
0.96
0.96
0.96
0.96
0.96
Table 34: Mains supply 3 x 200–240 V AC — Normal overload 110% for 1 minute, 30HP - 60HP
Frequency type designation
0300
0400
0500
0600
IP20/chassis
6)
C3
C3
C4
C4
IP21/NEMA 1
C1
C1
C2
C2
IP55/Type 12
C1
C1
C2
C2
IP66/NEMA 4X
C1
C1
C2
C2
Typical shaft output [HP]
30
40
50
60
Typical shaft output [HP] at 208 V
30
40
50
60
Output current
Continuous (3 x 200–240 V) [A]
88.0
115
143
170
Intermittent (3 x 200–240 V) [A]
96.8
127
157
187
Continuous KVA (208 V VA) [kVA]
31.7
41.4
51.5
61.2
Maximum input current
Continuous (3 x 200–240 V) [A]
80.0
104.0
130.0
154.0
Intermittent (3 x 200–240 V) [A]
88.0
114.0
143.0
169.0
Additional specifications
Estimated power loss at rated maximum load [W]
4)
845
1140
1353
1636
IP20 maximum cable cross-section (mains, brake, motor, and load sharing)
150 (300 mcm)
IP21, IP55, IP66 maximum cable cross-section (mains, motor) [mm
2
/AWG]
150 (300 mcm)
IP21, IP55, IP66 maximum cable cross-section (brake, load sharing) [mm
2
/
AWG]
95 (3/0)
Weight enclosure IP20 [kg]
35
35
50
50
Weight enclosure IP21 [kg]
45
45
65
65
Weight enclosure IP55 [kg]
45
45
65
65
Weight enclosure IP66 [kg]
45
45
65
65
Efficiency
3)
0.97
0.97
0.97
0.97
Technical Specification
Aquavar
®
Intelligent Pump Controller INSTRUCTION MANUAL
123