Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual
Page 126

Table 35: Mains supply 3 x 380–480 V AC — Normal overload 110% for 1 minute, 1.5HP - 10HP
Frequency type designation
0015
0020
0030
0050
0075
0100
Typical shaft output [HP]
1.5
2
3
5
7.5
10
Typical shaft output [HP] at 460 V
1.5
2.0
2.9
5.0
7.5
10
IP20/Chassis
5)
A2
A2
A2
A2
A3
A3
IP55/Type 12
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
IP66/NEMA 4X
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
Output current
Continuous (3 x 280–440 V) [A]
3
4.1
5.6
10
13
16
Intermittent (3 x 380–440 V) [A]
3.3
4.5
6.2
11
14.3
17.6
Continuous (3 x 441–480 V) [A]
2.7
3.4
4.8
8.2
11
14.5
Intermittent (3 x 441–480 V) [A]
3.0
3.7
5.3
9.0
12.1
15.4
Continuous kVA (400 V AC) [kVA]
2.1
2.8
3.9
6.9
9.0
11.0
Continuous kVA (460 V AC) [kVA]
2.4
2.7
3.8
6.5
8.8
11.6
Maximum input current
Continuous (3 x 380–440 V) [A]
2.7
3.7
5.0
9.0
11.7
14.4
Intermittent (3 x 380–440 V) [A]
3.0
4.1
5.5
9.9
12.9
15.9
Continuous (3 x 441–480 V) [A]
2.7
3.1
4.3
7.4
9.9
13.0
Intermittent (3 x 441–480 V) [A]
3.0
3.4
4.7
8.1
10.9
14.3
Additional specifications
Estimated power loss at rated maximum load [W]
4)
58
62
88
124
187
255
IP20, IP21 maximum cable cross-section (mains, motor, brake, and load sharing)
[mm
2
/AWG]
2)
4, 4, 4 (12, 12, 12)
(min. 0.2(24))
IP55, IP66 maximum cable cross-section (mains, motor, brake, and load sharing)
[mm
2
/AWG]
2)
4, 4, 4 (12, 12, 12)
Maximum cable cross-section with disconnect
6, 4, 4 (10, 12, 12)
Weight enclosure IP20 [kg]
4.8
4.9
4.9
4.9
6.6
6.6
Weight enclosure IP21 [kg]
Weight enclosure IP55 [kg] (A4/A5)
9.7/13.
5
9.7/13.
5
9.7/13.
5
9.7/13.
5
14.2
14.2
Weight enclosure IP66 [kg] (A4/A5)
9.7/13.
5
9.7/13.
5
9.7/13.
5
9.7/13.
5
14.2
14.2
Efficiency
3)
0.96
0.97
0.97
0.97
0.97
0.97
Table 36: Mains supply 3 x 380–480 V AC — Normal overload 110% for 1 minute, 15HP - 40HP
Frequency type designation
0150
0200
0250
0300
0400
Typical shaft output [HP]
15
20
25
30
40
Typical shaft output [HP] at 460 V
15
20
25
30
40
IP20/chassis
6)
B3
B3
B3
B4
B4
IP21/NEMA 1
B1
B1
B1
B2
B2
IP55/Type 12
B1
B1
B1
B2
B2
IP66/NEMA 4X
B1
B1
B1
B2
B2
Output current
Continuous (3 x 380–439 V) [A]
24
32
37.5
44
61
Intermittent (3 x 380–439 V) [A]
26.4
35.2
41.3
48.4
67.1
Technical Specification
124