Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual
Page 114

Warning/Alarm
Description
Cause
Remedy
10 — Motor overload temperature According to the electronic
thermal protection (ETR), the
motor is too hot. Select whether
the frequency converter gives a
warning or an alarm when the
counter reaches 100% in 1–90
Motor Thermal Protection.
The fault occurs when the motor is
overloaded by more than 100% for
too long.
Check for motor overheating.
Check if the motor is mechanically
overloaded.
Check that the motor current set in
[1–24] Motor Current is correct.
11 — Motor thermistor over temp The thermistor might be
disconnected. Select whether the
frequency converter gives a
warning or an alarm in 1–90
Motor Thermal Protection.
Check for motor overheating.
Check if the motor is mechanically
overloaded.
When using terminal 53 or 54,
check that the thermistor is
connected correctly between
either terminal 53 or 54 (analog
voltage input) and terminal 50
(+10 V supply) and that the
terminal switch for 53 or 54 is set
for voltage. Check [1–93]
Thermistor Source selects terminal
53 or 54.
When using digital inputs 18 or
19, check that the thermistor is
connected correctly between
either terminal 18 or 19 (digital
input PNP only) and terminal 50.
Check [1–93] Thermistor Source
selects terminal 18 or 19.
12 — Torque limit
The torque has exceeded the value
in 4–16 Torque Limit Motor Mode
or the value in 4–17 Torque Limit
Generator Mode. 14–25 Trip Delay
at Torque Limit can change this
from a warning only condition to a
warning followed by an alarm.
If the motor torque limit is
exceeded during ramp up, extend
the ramp up time.
If the generator torque limit is
exceeded during ramp down,
extend the ramp down time.
If torque limit occurs while
running, possibly increase the
torque limit. Be sure the system
can operate safely at a higher
torque.
Check the application for excessive
current draw on the motor.
13 — Over current
The inverter peak current limit
(approx. 200% of the rated
current) is exceeded. The warning
lasts about 1.5 seconds, then the
frequency converter trips and
issues an alarm. This fault may be
caused by shock loading or fast
acceleration with high inertia
loads. If extended mechanical
brake control is selected, trip can
be reset externally.
Remove power and check if the
motor can be turned.
Check that the motor size matches
the frequency converter.
Check parameters 1–20 through
1–25 for correct motor data.
14 — Ground/Earth fault
There is current from the output
phases to ground, either in the
cable between the frequency
converter and the motor or in the
motor itself.
Remove power to the frequency
converter and repair the earth
fault.
Check for ground faults in the
motor by measuring the resistance
to ground of the motor leads and
the motor megohmmeter.
Warnings and alarms
112
Aquavar
®
Intelligent Pump Controller INSTRUCTION MANUAL