Operating Instruction

56

other following pumps. (Start-Value = REQUIRED VALUE –ACT. VALUE DEC.)

Press on the Technovar to change to

10.22.3 Release frequency of the following controller

ENABLE SEQ. CTL.

58.0 Hz

Release of the follow-up pump only when the start-

value

is reached and the lead pump

has reached the programmed frequency. (Adjustable from 0.0 Hz to 70 Hz).
If you do not want to start a following pump this value has to be set higher than the
maximum frequency.

This parameter is also used to start a constant speed pump, when Simple Multicontr. is
set). When this frequency level is reached, the potential free contact of the relay X2/5 –

X2/6 will be closed.

Press on the Technovar to change to

10.22.4 Switch Interval

SWITCH INTERVAL

12 hours

for changing the master pump and follow-up pump in
order to achieve even operating hours of the pumps

Adjustable between 1 hour and 100 hours. If it is set higher than 100 hours, the automatic

changeover is deactivated).
Manual change of master pump in the 1

st

display with the -button.

Press on the Technovar to change to