beautypg.com

Bell & Gossett 193 TECHNOVAR VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED AJUSTABLE FREQUENCY DRIVE User Manual

Page 31

background image

Operating Instruction

31

8

Typical applications

8.1 Control

By means of the built-in Technovar controller acc. to constant pressure by pressure
transmitter and/or acc. to constant flow by flow-meter or orifice plate with differential

pressure transmitter and differential pressure transmitter or - if required - acc. to external
manual control by reference 4 - 20 mA DC (only for special applications).

8.2

The Main Menu Setting

There are ten display screens in the main menu which will allow you set the required system
pressure, save it, and turn the system on. Several of these display screens were already used
during the test run. After power has been turned on, the “Power on” light should illuminate
and the display should show “No Autostart – disable inverter”.

Instructions:

Check the green POWER light

NO Autostart

disable inverter

Press the button to advance the display to

INVERTER STOP

ON -> START

Press to advance the display to

REQUIRED VALUE

X.XX psi

REQUIRED VALUE

Set the desired set pressure with either or . If several pumps are connected via the RS-
485 interface, one pump must be ready for operation when the set pressure is changed,

otherwise the set value will not be accepted by the follow-up pumps. Afterwards the new
required pressure has to be saved in all pumps.

Press to confirm and the display changes to

AUTO – START

OFF

AUTO – START

Select (ON) with the button or (OFF) with . Auto-start ON starts the pump automatically

again after an interruption of the power supply (power failure).

At the Auto-start setting OFF, the pump must be restarted manually by pressing the buttons

(OFF) and then (ON) after power failure.

Press and the display changes to:

ERROR 1

...................

Last error

Note:

All errors are only readable

Press the button to change to

Error before last error:

ERROR 2

...................