Operating Instruction

49

10.9 Minimum Frequency

MIN. FREQUENCY

0.0 Hz

Here you can set the minimum frequency between 0,0
and Max.frequency.

Attention!: If there is set f>fmin in the parameter CONFIG. FMIN the pump will not stop in

the normal mode. It will keep running with the set minimum frequency.
!! Possibility of overheating of the pump !!

Press on the Technovar to change to

10.10 Operation at the minimum frequency

CONFIG FMIN

f => fmin

If you have selected „f->0“ the frequency will go

down to the selected minimum frequency.

Then the inverter will keep running for the selected time and after this time the Technovar
will stop automatically.

If the selection is „f->f

min

“ you can not run the pump below the set minimum frequency. In

the controller, actuator and multi controller mode the pump will never run below the set

minimum frequency (the pump will only stop with an external on/off-(terminals X1/4 and
X1/5) or in case of a failure.

Press on the Technovar to change to

10.11 Delay time for shut off at minimum frequency

STOP-DELAY FMIN

5 s

After running the pump for this selected time at

minimum frequency, the pump will stop, if parameter

CONFIG. FMIN

it set to f Þ 0 Adjustable between 0 and 100s.

Press on the Technovar to change to

10.12 Boost

BOOST

5.0 %

The stated value determines the course of the
U/f-curve.

Setting of the motor starting voltage in % of rated voltage

.

Settings of 0...25% of maximum output voltage are possible. However, care should be taken

that settings are kept as low as possible so that the motor does not become thermally
overloaded at lower frequencies.

Press on the Technovar to change to