GE Industrial Solutions Entellisys Integrator’s Guide User Manual
Page 62

62
21
Bit field representing a 0 or 1 for Node 21
22
Bit field representing a 0 or 1 for Node 22
23
Bit field representing a 0 or 1 for Node 23
24
Bit field representing a 0 or 1 for Node 24
25
Bit field representing a 0 or 1 for Node 25
26
Bit field representing a 0 or 1 for Node 26
27
Bit field representing a 0 or 1 for Node 27
28
Bit field representing a 0 or 1 for Node 28
29
Bit field representing a 0 or 1 for Node 29
30
Not Used
31
Not Used
F726
ENUMERATION
SRCX curve type
0
Inverse time curve
1
Constant time curve
F727
ENUMERATION
SRCX Trip or Open setting
0
Open and don't activate lockout
1
Trip and activate lockout
F728
BITFIELD
Option Bit Vectors
F732 ENUMERATION
ZSI
Option
0
ST ZSI
1
GF ZSI
2
ST and GF ZSI
F733
ENUMERATION
ZSI Zone Tier Settings
0
ZSI Tier 0
1
ZSI Tier 1
2
ZSI Tier 2
3
ZSI Tier 3
F734
ENUMERATION
Contact IO Debounce values
0
Disabled
1
Enabled_00016
2
Enabled_00104
3
Enabled_04088
4
Enabled_32760
F735
ENUMERATION
Multipoint delay band settings
0
BAND 1
1
BAND 2
2
BAND 3
3
BAND 4
4
BAND 5
5
BAND 6
6
BAND 7
F736
UINT32
Contact Input Configuration Low Vector
0
0 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
1
1 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
2
2 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
3
3 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
4
4 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
5
5 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
6
6 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
7
7 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
8
8 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
9
9 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output