5CE7
SRC x Time Date Initial Energization
0 to 4294967295
---
1
F050
0
Source Settings (Read Only) (30 modules)
5CE9
SRC_X_Breaker_Service_Hours
0 to 4294967295
---
1
F003
0
Source Settings (Read/Write Setting) (30 modules)
5CEB
Reserved6 (5 items)
0 to 65535
---
1
F001
0
5CF0
SRC x UF Trip Enable
0 to 1
---
1
F102
0 (Disabled)
5CF1
SRC x UF Trip Pickup Setting
45 to 60
---
0.1
F001
450
5CF2
SRC x UF Trip Time Delay
0.1 to 600
---
0.1
F001
300
5CF3
SRC x UF Trip Blocking Voltage Enable
0 to 1
---
1
F102
0 (Disabled)
5CF4
SRC x UF Trip or Open setting
0 to 1
---
1
F727
1 (Trip and activate
lockout)
5CF5
SRC x UF Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
5CF6
SRC x UF Alarm Pickup Setting
45 to 60
---
0.1
F001
450
5CF7
SRC x UF Alarm Time Delay
0.1 to 600
---
0.1
F001
150
5CF8
SRC x UF Alarm Blocking Voltage Enable
0 to 1
---
1
F102
0 (Disabled)
5CF9
SRC x OF Trip Enable
0 to 1
---
1
F102
0 (Disabled)
5CFA
SRC x OF Trip Pickup Setting
50 to 70
---
0.1
F001
500
5CFB
SRC x OF Trip Time Delay
0.1 to 600
---
0.1
F001
300
5CFC
SRC x OF Trip Blocking Voltage Enable
0 to 1
---
1
F102
0 (Disabled)
5CFD
SRC x OF Trip or Open setting
0 to 1
---
1
F727
1 (Trip and activate
lockout)
5CFE
SRC x OF Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
5CFF
SRC x OF Alarm Pickup Setting
50 to 70
---
0.1
F001
500
5D00
SRC x OF Alarm Time Delay
0.1 to 600
---
0.1
F001
150
5D01
SRC x OF Alarm Blocking Voltage Enable
0 to 1
---
1
F102
0 (Disabled)
5D02
SRC x HRGF Enable
0 to 1
---
1
F102
0 (Disabled)
5D03
SRC x HRGF Pickup
2 to 10
---
0.1
F001
20
5D04
SRC x HRGF Delay
0.5 to 5
---
0.1
F001
5
5D05
SRC x HRGF Ground Resistance
5 to 500
---
1
F001
5
5D06
SRC x HRGF CT Rating
10 to 10
---
1
F001
10
5D07
SRC x Settings Reserved (41 items)
0 to 65535
---
1
F001
0
5D30
...Repeated for module number 2
5DD6
...Repeated for module number 3
5E7C
...Repeated for module number 4
5F22
...Repeated for module number 5
5FC8
...Repeated for module number 6
606E
...Repeated for module number 7
6114
...Repeated for module number 8
61BA
...Repeated for module number 9
6260
...Repeated for module number 10
6306
...Repeated for module number 11
63AC
...Repeated for module number 12
6452
...Repeated for module number 13
64F8
...Repeated for module number 14
659E
...Repeated for module number 15