GE Industrial Solutions Entellisys Integrator’s Guide User Manual
Page 19

19
Modbus Memory Map
NOTE: A multiplier factor may be necessary in cases where an integer value is returned but the Range and/or Step imply a
greater precision. In these cases, it is necessary to divide the returned value by 10 for a step of "0.1" or "0.5"; by 100 for a step of
".01"; and so on. Similarly, it is necessary to multiply by these factors prior to writing a settings value. This note does
not apply
to any step value greater than 1 (a step of "10" does not require a multiplier, for example). This note also does not apply to
values returned in floating point format. See the format codes at the end of the map for more information.
NOTE: Discrete I/O output state registers (Contact Output x State – register range from x9180 to x91FF and Contact Output
States – register range from xB256 to 0xB25D) contain correct information only when FlexLogic Active register (x0034) contains
value 1 (yes).
Addr
Register Name
Range Units Step Format Factory Default
Product Information (Read Only)
0000
Product Type
0 to 2
---
1
F716
0 (Low Voltage
Switchgear)
0001
Serial Number
---
---
---
F203
"0"
0009
External Ethernet MAC Address
---
---
---
F072
0
000C
Reserved (3 items)
---
---
---
F001
0
000F
CPU Hardware Version
0 to 655.35
---
0.01
F001
100
0010
CPU Firmware Version
0 to 655.35
---
0.01
F001
100
0011
CPU Firmware Boot Code Version
0 to 655.35
---
0.01
F001
100
0012
Build Date
---
---
---
F200
"0"
0026
Synchronizer Board Status
0 to 1
---
1
F102
0 (Disabled)
0027
Synchronizer Board Frequency Setting
50 to 60
Hz
10
F001
60
0028
Last Energy Clear Date
0 to 4294967295
---
1
F050
0
002A
Last CPU Commissioned Date
0 to 4294967295
---
1
F050
0
002C
Expected Node Protocol Version
0 to 655.35
---
0.01
F001
0
002D
Summary Number
---
---
---
F205
"0"
0033
Line Up
0 to 99
---
1
F001
1
0034
FlexLogic Active
0 to 1
---
1
F126
0 (No)
0035
Reserved (203 items)
---
---
---
F001
0
Installation (Read/Write Setting)
0100
CPU ID
0 to 1
---
1
F717
0 (CPU A)
0101
CPU Commissioned
0 to 1
---
1
F102
0 (Disabled)
0102
CPU Name
---
---
---
F200
"UNNAMED"
0116
System Frequency
50 to 60
Hz
10
F001
60
0117
Phase Rotation
0 to 1
---
1
F106
0 (ABC)
0118
Reserved (232 items)
---
---
---
F001
0
Clock (Read/Write Command)
0200
RTC Set Time
0 to 4294967295
---
1
F050
0
Clock (Read Only)
0202
Date Time Changed
0 to 4294967295
---
1
F050
0
0204
Reserved (8 items)
---
---
---
F001
0