GE Industrial Solutions Entellisys Integrator’s Guide User Manual
Page 43

43
C212
...Repeated for module number 4
C262
...Repeated for module number 5
C2B2
...Repeated for module number 6
C302
...Repeated for module number 7
C352
...Repeated for module number 8
C3A2
...Repeated for module number 9
C3F2
...Repeated for module number 10
C442
...Repeated for module number 11
C492
...Repeated for module number 12
C4E2
...Repeated for module number 13
C532
...Repeated for module number 14
C582
...Repeated for module number 15
C5D2
...Repeated for module number 16
C622
...Repeated for module number 17
C672
...Repeated for module number 18
C6C2
...Repeated for module number 19
C712
...Repeated for module number 20
C762
...Repeated for module number 21
C7B2
...Repeated for module number 22
C802
...Repeated for module number 23
C852
...Repeated for module number 24
C8A2
...Repeated for module number 25
C8F2
...Repeated for module number 26
C942
...Repeated for module number 27
C992
...Repeated for module number 28
C9E2
...Repeated for module number 29
CA32
...Repeated for module number 30
ZSI MSGF Tier Settings (Read/Write Setting) (4 modules)
CA82
MSGF ZSI Zone 1 GRPx Tier Settings (16 items)
0 to 3
---
1
F733
0 (ZSI Tier 0)
CA92
MSGF ZSI Zone 2 GRP x Tier Settings (16 items)
0 to 3
---
1
F733
0 (ZSI Tier 0)
CAA2
MSGF ZSI Zone 3 GRP x Tier Settings (16 items)
0 to 3
---
1
F733
0 (ZSI Tier 0)
CAB2
MSGF ZSI Zone 4 GRP x Tier Settings (16 items)
0 to 3
---
1
F733
0 (ZSI Tier 0)
CAC2
MSGF ZSI Reserved (16 items)
0 to 65535
---
1
F001
0
CAD2
...Repeated for module number 2
CB22
...Repeated for module number 3
CB72
...Repeated for module number 4
Zone x MSGF Settings (Read/Write Setting) (4 modules)
CBC2
Zone x MSGF Trip Pickup Setting (16 items)
30 to 1200
---
1
F001
1200
CBD2
Zone x MSGF Alarm Pickup Setting (16 items)
30 to 1200
---
1
F001
1200
CBE2
Zone x MSGF Trip Delay Band Setting (16
items)
0 to 6
---
1
F735
2 (BAND 3)
CBF2
Zone x MSGF Alarm Delay Band Setting (16
items)
0 to 6
---
1
F735
2 (BAND 3)
CC02
Zone x MSGF Trip I2T Curve (16 items)
0 to 1
---
1
F102
0 (Disabled)