500B
SRC x Product Type
0 to 2
---
1
F716
0 (Low Voltage
Switchgear)
500C
SRC x NodeProt Rating Switch
0 to 65535
---
1
F001
0
500D
SRC x NodeProt LT Setting
0 to 655.35
---
0.01
F001
0
500E
SRC x NodeProt IOC Threshold Setting
0 to 655.35
---
0.01
F001
0
500F
SRC x NodeProt Ground Fault Setting
0 to 1
---
1
F102
0 (Disabled)
5010
SRC x NodeProt Short Time Setting
0 to 1
---
1
F102
0 (Disabled)
5011
SRC x Node Internal Diagnostics
0 to 65535
---
1
F701
0
5012
SRC x Node System Diagnostics 1
0 to 65535
---
1
F702
0
5013
SRC x Node System Diagnostics 2
0 to 65535
---
1
F703
0
5014
SRC x Node Hardware Diagnostics
0 to 65535
---
1
F704
0
5015
SRC x Node Physical Status
0 to 65535
---
1
F708
0
5016
SRC x Node Logic and Trip Status
0 to 65535
---
1
F709
0
5017
SRC x Node Last Trip Sequence Number
0 to 4294967295
---
1
F003
0
5019
SRC x Reflected CPU Diagnostics
0 to 65535
---
1
F706
0
501A
SRC x Reflected CPU 0 Command
0 to 65535
---
1
F707
0
501B
SRC x Reflected CPU 1 Command
0 to 65535
---
1
F707
0
501C
SRC x Fan Status
0 to 1
---
1
F108
0 (Off)
501D
SRC x CT Rating Node Report
0 to 65535
---
1
F001
0
501E
SRC x Node Serial Number
---
---
---
F205
(none)
5024
SRC x Node Status Reserved (43 items)
0 to 1
---
1
F001
0
504F
...Repeated for module number 2
509E
...Repeated for module number 3
50ED
...Repeated for module number 4
513C
...Repeated for module number 5
518B
...Repeated for module number 6
51DA
...Repeated for module number 7
5229
...Repeated for module number 8
5278
...Repeated for module number 9
52C7
...Repeated for module number 10
5316
...Repeated for module number 11
5365
...Repeated for module number 12
53B4
...Repeated for module number 13
5403
...Repeated for module number 14
5452
...Repeated for module number 15
54A1
...Repeated for module number 16
54F0
...Repeated for module number 17
553F
...Repeated for module number 18
558E
...Repeated for module number 19
55DD
...Repeated for module number 20
562C
...Repeated for module number 21
567B
...Repeated for module number 22
56CA
...Repeated for module number 23
5719
...Repeated for module number 24