GE Industrial Solutions Entellisys Integrator’s Guide User Manual
Page 35

35
5CB0
SRC x OV Trip Time Delay
0.5 to 600
---
0.5
F001
300
5CB1
SRC x OV Trip Phase Requirement
1 to 3
---
1
F001
1
5CB2
SRC x OV Trip Open or Trip Setting
0 to 1
---
1
F727
1 (Trip and activate
lockout)
5CB3
SRC x OV Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
5CB4
SRC x OV Alarm Pickup Threshold
105 to 125
---
1
F001
120
5CB5
SRC x OV Alarm Time Delay
0.5 to 600
---
0.5
F001
150
5CB6
SRC x OV Alarm Phase Requirement
1 to 3
---
1
F001
1
5CB9
Reserved2 (7 items)
0 to 65535
---
1
F001
0
5CBE
SRC x PL Trip Enable
0 to 1
---
1
F102
0 (Disabled)
5CBF
SRC x PL Trip Pickup Setting
8 to 50
---
1
F001
8
5CC0
SRC x PL Trip Time Delay
0.5 to 600
---
0.5
F001
300
5CC1
SRC x PL Trip Block Volt Enable
0 to 1
---
1
F102
0 (Disabled)
5CC2
SRC x PL Open or Trip Setting
0 to 1
---
1
F727
1 (Trip and activate
lockout)
5CC3
SRC x PL Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
5CC4
SRC x PL Alarm Pickup Setting
8 to 50
---
1
F001
8
5CC5
SRC x PL Alarm Time Delay
0.5 to 600
---
0.5
F001
150
5CC6
SRC x PL Alarm Block Volt Enable
0 to 1
---
1
F102
0 (Disabled)
Source Settings (Read Only) (30 modules)
5CC7
SRC x PL Trip Voltage Setting
5 to 5
---
1
F001
5
5CC8
SRC x PL Alarm Blocking Voltage Setting
5 to 5
---
1
F001
5
Source Settings (Read/Write Setting) (30 modules)
5CC9
Reserved3 (3 items)
0 to 65535
---
1
F001
0
5CCC
SRC x Rev Power Trip Enable
0 to 1
---
1
F102
0 (Disabled)
5CCD
SRC x Rev Power Trip Pickup Setting
10 to 990
---
10
F001
990
5CCE
SRC x Rev Power Trip Time Delay
0.5 to 600
---
0.5
F001
300
5CCF
SRC x Rev Power Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
5CD0
SRC x Rev Power Alarm Pickup Setting
10 to 990
---
10
F001
990
5CD1
SRC x Rev Power Alarm Time Delay
0.5 to 600
---
0.5
F001
150
5CD2
SRC x Rev Power Trip or Open
0 to 1
---
1
F727
1 (Trip and activate
lockout)
5CD3
Reserved4 (4 items)
0 to 65535
---
1
F001
0
5CD7
SRC x High Curr Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
5CD8
SRC x High Curr Alarm Pickup Setting
50 to 200
---
5
F001
200
5CD9
SRC x High Curr Alarm Time Delay
1 to 15
---
1
F001
15
5CDA
Reserved5 (5 items)
0 to 65535
---
1
F001
0
5CDF
SRC x Total Breaker Operations
0 to 65535
---
1
F001
0
5CE0
SRC x Total Breaker No Load Operations
0 to 65535
---
1
F001
0
5CE1
SRC x Total Breaker Load Operations
0 to 65535
---
1
F001
0
5CE2
SRC x Total Breaker Fault Operations
0 to 65535
---
1
F001
0
5CE3
SRC x Breaker Percent Load Life
0 to 655.35
---
0.01
F001
0
Source Settings (Read Only) (30 modules)
5CE4
SRC x Percent Mechanical Life
0 to 655.35
---
0.01
F001
0
Source Settings (Read/Write Setting) (30 modules)
5CE5
SRC x Time Date Last Breaker Operation
0 to 4294967295
---
1
F050
0