44
CC12
Zone x MSGF Alarm I2T Curve (16 items)
0 to 1
---
1
F102
0 (Disabled)
CC22
Zone x MSGF Trip Enabled (16 items)
0 to 1
---
1
F102
0 (Disabled)
CC32
Zone x MSGF Alarm Enabled (16 items)
0 to 1
---
1
F102
0 (Disabled)
CC42
Zone x MSGF Backup Enabled (16 items)
0 to 1
---
1
F102
0 (Disabled)
CC52
Zone x MSGF Backup Time Date Enabled (16
items)
0 to 1
---
1
F102
0 (Disabled)
CC62
Zone x MSGF Trip or Open
0 to 1
---
1
F727
0 (Open and don't
activate lockout)
CC63
Zone x MSGF Reserved (16 items)
0 to 65535
---
1
F001
0
CC73
...Repeated for module number 2
CD24
...Repeated for module number 3
CDD5
...Repeated for module number 4
Zone x BD Settings (Read/Write Setting) (4 modules)
CE8A
Zone x BD Trip Pickup Setting (16 items)
30 to 22000
---
1
F001
1200
CE9A
Zone x BD Alarm Pickup Setting (16 items)
30 to 22000
---
1
F001
1200
CEAA
Zone x BD Trip Pickup Setting2 (16 items)
30 to 22000
---
1
F001
1200
CEBA
Zone x BD Alarm Pickup Setting2 (16 items)
30 to 22000
---
1
F001
1200
CECA
Zone x BD Trip Delay Band Setting (16 items)
0 to 6
---
1
F735
2 (BAND 3)
CEDA
Zone x BD Alarm Delay Band Setting (16
items)
0 to 6
---
1
F735
2 (BAND 3)
CEEA
Zone x BD Trip Delay Band Setting2 (16 items)
0 to 6
---
1
F735
2 (BAND 3)
CEFA
Zone x BD Alarm Delay Band Setting2 (16
items)
0 to 6
---
1
F735
2 (BAND 3)
CF0A
Zone x BD Trip Enabled (16 items)
0 to 1
---
1
F102
0 (Disabled)
CF1A
Zone x BD Alarm Enabled (16 items)
0 to 1
---
1
F102
0 (Disabled)
CF2A
Zone x BD Backup Enabled (16 items)
0 to 1
---
1
F102
0 (Disabled)
CF3A
Zone x BD Backup Time Delta Enabled (16
items)
0 to 1
---
1
F102
0 (Disabled)
CF4A
Zone x BD Trip or Open
0 to 1
---
1
F727
0 (Open and don't
activate lockout)
CF4B
Zone x BD Reserved (16 items)
0 to 65535
---
1
F001
0
CF5B
...Repeated for module number 2
D02C
...Repeated for module number 3
D0FD
...Repeated for module number 4
Zone x Summation Settings (Read/Write Setting) (2 modules)
D1D2
Zone x Summation MSGF Trip Delay Band
Setting (16 items)
0 to 6
---
1
F735
2 (BAND 3)
D1E2
Zone x Summation MSGF Alarm Delay Band
Setting (16 items)
0 to 6
---
1
F735
2 (BAND 3)
D1F2
Zone x Summation MSGF Trip I2T (16 items)
0 to 1
---
1
F102
0 (Disabled)
D202
Zone x Summation MSGF Alarm I2T Curve (16
items)
0 to 1
---
1
F102
0 (Disabled)
D212
Zone x Summation MSGF Trip Enabled (16
items)
0 to 1
---
1
F102
0 (Disabled)
D222
Zone x Summation MSGF Alarm Enabled (16
items)
0 to 1
---
1
F102
0 (Disabled)
D232
Zone x Summation MSGF Trip Pickup Setting
(16 items)
30 to 1200
---
1
F001
1200
D242
Zone x Summation MSGF Alarm Pickup
30 to 1200
---
1
F001
1200