0 ge zenith series monitor alarm description – GE Industrial Solutions GE ZENITH SERIES MDU User Manual
Page 40

GE Zenith Series Monitor Alarm Description
GE Z
ENITH
C
ONTROLS
MDU Owner’s Manual
601 S
HILOH
R
OAD
January 2013
Plano, TX 75074
Page 40
7.0 GE Zenith Series Monitor Alarm Description
A
LARM
N
AME
A
LARM
M
ESSAGE
A
LARM
D
ESCRIPTION
Input Phase Rotation
"PHASE ROTATION"
If the phase rotation is incorrect on the unit's input, the
unit will alarm.
High Temperature Transformer
"THERM OVERTEMP”
If the 180
o
C thermal switches located in the windings of
the transformer reach their rating or better, the unit
will alarm. First part of a two stage high transformer
temperature alarm system.
High Temperature Transformer
Shutdown
"THERM HIGHTEMP"
If the 200
o
C thermal switches located in the windings of
the transformer reach their rating or better, the unit's
main circuit breaker will shunt trip, shutdown the unit.
Second part of a two stage high transformer
temperature alarm system.
Input Voltage Phase A-B High
“INPUT VOLT AB HIGH"
If the input voltage on phase A-phase B goes above the
preset level line to line, the unit will alarm.
Input Voltage Phase B-C High
“INPUT VOLT BC HIGH"
If the input voltage on phase B-phase C goes above the
preset level line to line, the unit will alarm.
Input Voltage Phase C-A High
"INPUT VOLT CA HIGH"
If the input voltage on phase C-phase A goes above the
preset level line to line, the unit will alarm.
Input Voltage Phase A-B Low
“INPUT VOLT AB LOW"
If the input voltage on phase A-phase B goes below the
preset level line to line, the unit will alarm.
Input Voltage Phase B-C Low
“INPUT VOLT BC LOW"
If the input voltage on phase B-phase C goes below the
preset level line to line, the unit will alarm.
Input Voltage Phase C-A Low
"INPUT VOLT CA LOW"
If the input voltage on phase C-phase A goes below the
preset level line to line, the unit will alarm.
Output Voltage Line A-B High
“OUTPUT VOLT AB HIGH"
If the output voltage on line A-line B goes above the
preset level line to line, the unit will alarm.
Output Voltage Line B-C High
" OUTPUT VOLT BC HIGH"
If the output voltage on line B-line C goes above the
preset level line to line, the unit will alarm.
Output Voltage Line C-A High
" OUTPUT VOLT CA HIGH"
If the output voltage on line C-line A goes above the
preset level line to line, the unit will alarm.
Output Voltage Line A-B Low
" OUTPUT VOLT AB LOW"
If the output voltage on line A-line B goes below the
preset level line to line, the unit will alarm.
Output Voltage Line B-C Low
"OUTPUT VOLT BC LOW”
If the output voltage on line B-line C goes below the
preset level line to line, the unit will alarm.
Output Voltage Line C-A Low
"OUTPUT VOLT CA LOW"
If the output voltage on line C-line A goes below the
preset level line to line, the unit will alarm.
Output Voltage Line
A - Neutral High
“OUTPUT VOLT AN HIGH"
If the output voltage on line A-Neutral goes above the
preset level line to Neutral, the unit will alarm.
Output Voltage Line
B - Neutral High
“OUTPUT VOLT BN HIGH"
If the output voltage on line B-Neutral goes above the
preset level line to Neutral, the unit will alarm.
Output Voltage Line
C - Neutral High
“OUTPUT VOLT CN HIGH"
If the output voltage on line C-Neutral goes above the
preset level line to Neutral, the unit will alarm.