Installation guide, Amp1h5 – GE Industrial Solutions AMP1H5 User Manual
Page 20

TM
AMP1H5
INSTALLATION GUIDE
ZL0115-0A
PAGE 20
©2013 For technical support please contact
01132
DET-785
our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)
#
Object_Name
Description
R/W
NV
Units
Range
Additional information
AI40
Pulse_Count_1
Pulse Count #1
R
NV
#
0 - 4294967040
Running count of contact closures on Pulse1 input since
last reset. Write 16498 (0x4072) to the Present_Value
property of Analog_Value object AV1 to reset both
Pulse Counters to 0.
AI41
Pulse_Count_2
Pulse Count #2
R
NV
#
0 - 4294967040
Pulse Count 2; Running count of contact closures on
Pulse2 input since last reset. Write 16498 (0x4072) to
the Present_Value property of Analog_Value object
AV1 to reset both Pulse Counters to 0.
AI42
KWH_A
Real Energy
Consumption
Phase A
R
NV
kWh
0 - 3.4+E38
AI43
KWH_B
Real Energy
Consumption
Phase B
R
NV
kWh
0 - 3.4+E38
AI44
KWH_C
Real Energy
Consumption
Phase C
R
NV
kWh
0 - 3.4+E38
AI45
Max_Power
Theoretical
Maximum System
Power
R
NV
kW
0 - 1.84467e19
Theoretical Maximum System Power – This is the
theoretical maximum power the meter expects to
see on a service. It is calculated by the meter from the
System Type (in object AV2), CT Size (in object AV3),
and System Voltage (in object AV6) - Power Factor is
assumed to be unity. The register is updated whenever
the user changes any of these parameters.
AI46
Reserved_AI46
Reserved
R
0
Returns QNAN or any value
AI47
Energy Resets
Count of Energy
Accumulator Resets
R
NV
0 - 32767
Running count of how many times the energy counter
has been reset
AI48
Reserved_AI48
Reserved
R
0
Returns QNAN or any value
AI49
Reserved_AI49
Reserved
R
0
Returns QNAN or any value
AI50
Power Up Count
Power Up Counter
R
NV
0 - 32767
Running count of product power-up cycles (Control
Power)
AI51
Ouput Config
Ouput Configuration R
NV
0 - 15
Returns “0”
AI52
Reserved_AI52
Alert Summary
Register
R
0 - 32767
This contains a decimal value that represents the status
of all Binary_Object alert values in one number that
can be read without having to access mulitple objects.
It is a decimal representation of a 15-bit hexidecimal
value produced by combining the 15 alert bits into one
number, where the bit value of Object BI1 is the least
significant bit and BI15 is the most significant bit.