AMP1H5

INSTALLATION GUIDE

ZL0115-0A

PAGE 12

©2013 For technical support please contact

01132

DET-785

our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)

Next

Set Passwords:

SETUP - The Password to enter the SETUP menu.

RESET - The Password to enter the RESET menu.

RESET

--------

00000

SPASS

Setup

Passwords

SETUP

--------

00000

Back

Next

SDMND

INTRV

--------

6

5

4

3

2

1

Demand

SEC

--------

00900

Back

Set Demand Interval:

INTRV - The number of Sub-Intervals (1 to 6) in a

Demand Interval

. Default is 1 (block demand).

SEC - Sub-Interval length in seconds. Default is

900 (15 minutes). Set to 0 for external sync-to-

comms.

Next

S DIS

Display

Units

UNITS

--------

IEEE

IEC

Back

Set Display Units: +/- to switch between:

IEEE – VLL VLN W VAR VA Units.

IEC - U V P Q S Units.

To Setup p. 1 “S PWR”

SPLOS

Back

IMBAL

--------

0.25

Next

VOLTS

--------

0.10

Set Phase Loss:

VOLTS - Phase Loss Voltage: The fraction of the system

voltage below which Phase Loss Alarm is on. For system

types with neutral, the Line to Neutral voltage is also

calculated and tested. If the System Voltage is 600 and the

fraction is set to 0.10, then the Phase Loss threshold will be

60 volts.

IMBAL - Phase Loss Imbalance: The fractional difference

in Line to Line voltages above which Phase Loss Alarm is

on. For system types with neutral, the Line to Neutral

voltages are also tested. For system types 1+N (10) and 2

(11) , imbalance is not tested.

Phase

Loss

To Setup page 1 “S BAC”