1 tle series 225 - 500 parallel system start-up, Tle series 225 - 500 parallel system start-up, The safety screens are fixed in their position – GE Industrial Solutions TLE Series 225-500 User Manual User Manual
Page 69: Leds on synoptic diagram, Continue
![background image](/manuals/294743/69/background.png)
Critical Power
Modifications reserved
Page 69/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
7.3 PROCEDURES FOR TLE SERIES 225 - 500 PARALLEL SYSTEM
7.3.1 TLE Series 225 - 500 Parallel System start-up
WARNING !
Before proceeding to turn on the UPS system, ensure that the AC and DC external
isolators are OFF, and prevent their inadverted operation.
Ensure that the Output Load distribution can be powered and all the Output
Isolators are open.
This procedure must be performed for the first start-up following the installation, with the Parallel
System completely switched Off and not powered.
Open the front door on all UPS units and make sure that:
All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
The safety screens are fixed in their position.
The switches Q1, Q2 and CB3 (option) are open (Pos. O) and the external Battery protections must
be open (Pos. O).
TLE Series 225 & 250
TLE Series 400 & 500
LEDs on Synoptic Diagram
Q1
Load output switch
Q2
Manual Bypass switch
CB3
External battery switch (option)
LED 1
Rectifier
LED 2
Inverter
LED 3
Booster/ Battery charger
LED 4 Automatic Bypass
LED 5 LOAD on UPS
LED ALARM
LED LOAD PROTECTED
Command Inverter ON
Command Inverter OFF
Command
Module shutdown
Command
Module shutdown Reset
Command
System shutdown
Command
System shutdown Reset
1. Switch-ON the Utility voltage, on all UPS units, from the input distribution (both Rectifier and
bypass if separated).
The UPS performs a “Self-test”.
A successful termination of the tests will be indicated with Overall test
results “OK”.
Commissioning cannot be continued should one or more tests result
to be negative. Please contact in this case your Service Center.
At this stage the Electronic Power Supply and Control Panel are switched
ON and the Buzzer sounds.
Press “MUTE” key to reset Acoustical Alarm.
LED ALARM remains lit.
Continue ►
CB3
(Option)
ON
OFF
Q1
I ON
0 O
FF
TLES_UL_225-
250_S1_Switch
Q1-Q2_01
Q2
I ON
0 O
FF
TLES_UL_400-500_
S1_Switch Q1-Q2_
CB3_01
Q1
I ON
0 OF
F
Q2
I ON
0 OF
F
CB3
(Option)
ON
OFF