GE Industrial Solutions TLE Series 225-500 User Manual User Manual
Page 39

Critical Power
Modifications reserved
Page 39/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Code
Message
Description
4605
COMMAND IEMi OFF
The IEMi Operation Mode has been disabled or the
programmed time is expired.
4606
eBoost/IEMi ACTIVATION ALLOWED
eBoost/IEMi control signal has been cleared on the
Customer Interface Board (X1 - 11, 22).
Operating mode depends on scheduled activation
of the functions.
4607
eBoost/IEMi ACTIVATION INHIBITED
Customer Interface Board (X1 - 11, 22) received an
eBoost/IEMi control signal.
eBoost™ Operation Mode and IEMi Operation
Mode will be temporarily inhibited.
4609
eBoost INHIBITED - LOW LOAD
eBoost™ Operation Mode inhibited due to minimal
load not reached.
4699
BATTERY TEST IMPOSSIBLE
Automatic Battery Test is not possible due to:
-
No Utility Rectifier or Bypass.
-
Battery not fully charged.
-
Load is below 10% or above 80%.
Test is postponed for 1 week.
4763
REMOTE CONTROL ON
Inverter can be started or shut-down by remote
control.
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both
4764
REMOTE CONTROL OFF
Inverter cannot be started or shut-down by remote
control.
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both
4798
SERVICE KEY ACTIVATED
A valid Service Key has been entered.
It will no longer be requested in the next 6 hours.
4799
SERVICE KEY DEACTIVATED
The Service Key validity period has expired.