GE Industrial Solutions TLE Series 225-500 User Manual User Manual
Page 43

Critical Power
Modifications reserved
Page 43/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
HOURS/DAY
The number of eBoost™ Operation Mode hours per weekday “Monday to Sunday” is displayed in the
operation mode parameter window (ceiling value).
NOTE !
To avoid undesired eBoost™ Operation Mode, verify:
Date and Time.
eBoost™ screen how many hours of eBoost™ Operation Mode have been
selected for each day of the week.
NOTE !
The eBoost™ Operation Mode will become active only if the Load is supplied from
the Inverter.
eBoost™ Operation Mode is only possible if the UPS load exceeds a minimum
threshold (default 10% of the rated capacity).
In case no-load conditions, or anyway below said threshold, the UPS operates in VFI
mode.
TOUCH SCREEN
This screen permits the adjustment
(“CALIBRATE” key) of the LCD’s “Touch
Screen” sensitivity.
IDENTIFICATION SCREEN
ID
Number of UPS in the RPA Parallel
System (0 for single unit).
Model
UPS model, power range and series
number.
S/N
The UPS serial number.
UPS SW version
The UPS software version.
Display SW version
The LCD display software version.