3 product specification – SENA Rhio10 User Manual
Page 8

8
1.3 Product Specification
10 Base-T Ethernet with RJ45 Ethernet connector
Network Interface
Supports static and dynamic IP address
Digital Input
-Number of channels: 12
-Input type: Voltage
-Input circuitry: Optically isolated photo-coupler
-Input range: 0V ∼ ±24V
OFF 0V ∼ ±1.2V, ON ±3.3V ∼ ±24V
-Sampling rate: 20ms
-Isolation voltage: 5KV
Digital Output
- Number of channels: 10
- Output type: Relay
- Rated load: 3A/240VAC
- Insulation resistance: 1000㏁ Min (DC500V)
- Isolation voltage(coil and contact): 4KV
- Reaction within 10ms
Analog Input
- Number of channels: 4
- Effective resolution: 10-bit
- Input type: Voltage, Direct Coupling
- Input range: 0V ∼ Aref (Analog reference voltage, 2~5V)
- Sampling rate: 1000 samples/sec
Protocol
ARP, IP/ICMP, TCP
telnet, DHCP client, PPPoE
Management
- Rhio Manager Windows Utility, Serial Console or Telnet
Software Support
- Windows MFC DLL library
- I/O configuration, I/O status monitoring/control
Diagnostic LED
- Power, Link, Act
- Digital Output, 1~10
- Digital Input, 1~12
- Analog Input, 1~4
Power
9V∼48VDC, Max. 5W
Environmental
- Operating temperature: 0℃ to 50℃
- Storage temperature: -20℃ to 66℃
- 90% Non-condensing