Modbus Help

Vlinx MESR321 Modbus Gateway

53

MESR321-xx_R001_2113_m

www.bb-elec.com

www.bb-europe.com


If the slave cannot respond appropriately for some other reason (e.g. it does not
recognize the function code), it will return a message containing an exception
response.

Hints and Tips

A few simple suggestions that may assist you if your system is experiencing
problems include:

Slowing down the polling rate may be helpful if power cycling doesn’t cure the
problem.

A common misperception is that every serial network must terminate with a

resistor. While this was true of early serial network configurations, it’s
typically the wrong answer.