Setup and Connections

Vlinx MESR321 Modbus Gateway

38

MESR321-xx_R001_2113m

www.bb-elec.com

www.bb-europe.com


2.

Method 2: Change the Modbus Gateway’s network settings to match your PC
using Console Mode

a. Connect a null modem serial cable (crossover cable) from Port 1 on

the Modbus Gateway to an available COM port on your PC.

b.

Enter Console Mode. Press and hold the Modbus Gateway’s Mode
switch for 2 to 10 seconds. Release the reset button. The READY LED
will blink for five seconds. This indicates that the Modbus Gateway is
re-booting in Console Mode.

c. When the Modbus Gateway has successfully restarted in Console

Mode, the READY LED will be OFF and the PORT 1 LED will be ON.

d. Open the Vlinx Modbus

Manager Software and select “Serial Port” as

the method to connect to the Modbus Gateway.

e. After logging in, click on .

f. Un-

check the box next to “I Want DHCP to setup the Network.”

g. Re-

configure the Modbus Gateway’s network settings to something

within the range of your PC’s network settings. For example:

PC Network Settings

IP Address = 192.168.0.1

Subnet Mask = 255.255.0.0

Default Gateway = 192.168.0.100

Change the Modbus Gateway’s network settings to:

IP Address = 192.168.0.50

Subnet Mask = 255.255.0.0

Default Gateway = 192.168.0.100

h. Save the settings and remove power from the Modbus Gateway.

i. Re-apply power. Open the Vlinx Modbus Manager Software and select

“Network” as the method to connect to the device.

Configuring the MESR321 via the Serial Port (Console Mode)