Advanced group parameters, English-10 – Grain Systems PNEG-526 User Manual
Page 90
![background image](/manuals/277780/90/background.png)
English-10
Advanced Group Parameters
No.
Parameter
Min/Max
Display/Options
Default
A051
A052
[Digital In1 Sel]
I/O Terminal 05
[Digital In2 Sel]
I/O Terminal 06
0/26
0 = “Not Used”
1 = “Acc 2 & Dec 2”
2 = “Jog”
3 = “Aux Fault”
4 = “Preset Freq”
5 = “Local”
6 = “Comm Port”
7 = “Clear Fault”
8 = “RampStop,CF”
9 = “CoastStop,CF”
10 = “DCInjStop,CF”
11 = “Jog Forward”
12 = “Jog Reverse”
13 = “10V In Ctrl”
14 = “20mA In Ctrl”
26 = “Anlg Invert”
4
A055 [Relay Out Sel]
0/21
0 = “Ready/Fault”
1 = “At Frequency”
2 = “MotorRunning”
3 = “Reverse”
4 = “Motor Overld”
5 = “Ramp Reg”
6 = “Above Freq”
7 = “Above Cur”
8 = “Above DCVolt”
9 = “Retries Exst”
10 = “Above Anlg V”
20 = “ParamControl”
21 = “NonRec Fault”
0
A056 [Relay Out Level]
0.0/9999
0.1
0.0
A067 [Accel Time 2]
0.0/600.0 Secs
0.1 Secs
20.0 Secs
A068 [Decel Time 2]
0.1/600.0 Secs
0.1 Secs
20.0 Secs
A069 [Internal Freq]
0.0/240.0 Hz
0.1 Hz
60.0 Hz
A070
A071
A072
A073
[Preset Freq 0]
(1)
[Preset Freq 1]
[Preset Freq 2]
[Preset Freq 3]
0.0/240.0 Hz
0.1 Hz
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
(1)
To activate [Preset Freq 0] set P038 [Speed Reference] to option 4.
A078 [Jog Frequency]
0.0/[Maximum Freq]
0.1 Hz
10.0 Hz
A079 [Jog Accel/Decel]
0.1/600.0 Secs
0.1 Secs
10.0 Secs
A080 [DC Brake Time]
0.0/90.0 Secs
0.1 Secs
0.0 Secs
A081 [DC Brake Level]
0.0/(Drive Amps × 1.8) 0.1 Amps
Amps × 0.05
A082 [DB Resistor Sel]
0/99
0 = Disabled
1 = Normal RA Res
2 = NoProtection
3-99 = % of Duty Cycle
0
A083 [S Curve %]
0/100%
1%
0% (Disabled)
A084 [Start Boost]
1/14
Settings in % of base voltage.
8
7 (5 HP Drives)
Only active when A125 [Torque Perf Mode] is
set to 0 “V/Hz”.
0 = “Custom V/Hz”
Variable Torque
Constant Torque
1 = “30.0, VT”
5 = “0.0, no IR”
10 = “10.0, CT”
2 = “35.0, VT”
6 = “0.0”
11 = “12.5, CT”
3 = “40.0, VT”
7 = “2.5, CT”
12 = “15.0, CT”
4 = “45.0, VT”
8 = “5.0, CT”
13 = “17.5, CT”
9 = “7.5, CT”
14 = “20.0, CT”
A088 [Maximum Voltage]
20/Rated Volts
1 VAC
Rated Volts
A089 [Current Limit]
0.1/(Drive Amps × 1.8) 0.1 Amps
Amps × 1.5
A090 [Motor OL Select]
0/2
0 = “No Derate”
1 = “Min Derate”
2 = “Max Derate”
0
A091 [PWM Frequency]
2.0/16.0 kHz
0.1 kHz
4.0 kHz
A092 [Auto Rstrt Tries]
0/9
1
0
A093 [Auto Rstrt Delay]
0.0/300.0 Secs
0.1 Secs
1.0 Secs
A094 [Start At PowerUp]
0/1
0 = “Disabled”
1 = “Enabled”
0
A095 [Reverse Disable]
0/1
0 = “Rev Enabled”
1 = “Rev Disabled”
0
A096 [Flying Start En]
0/1
0 = “Disabled”
1 = “Enabled”
0
A097 [Compensation]
0/3
0 = “Disabled”
1 = “Electrical”
2 = “Mechanical”
3 = “Both”
1
A098 [SW Current Trip]
0.0/(Drive Amps × 2)
0.1 Amps
0.0 (Disabled)
A099 [Process Factor]
0.1/999.9
0.1
30.0
A100 [Fault Clear]
0/2
0 = “Ready/Idle”
1 = “Reset Fault”
2 = “Clear Buffer”
0
A101 [Program Lock]
0/1
0 = “Unlocked”
1 = “Locked”
0
Input State of Digital In 1
(I/O Terminal 05)
Input State of Digital In 2
(I/O Terminal 06)
Frequency Source
Accel / Decel Parameter Used
(2)
0
0
[Preset Freq 0]
[Accel Time 1] / [Decel Time 1]
1
0
[Preset Freq 1]
[Accel Time 1] / [Decel Time 1]
0
1
[Preset Freq 2]
[Accel Time 2] / [Decel Time 2]
1
1
[Preset Freq 3]
[Accel Time 2] / [Decel Time 2]
(2)
When a Digital Input is set to “Accel 2 & Decel 2”, and the input is active, that input overrides the settings in this table.
See the PowerFlex 4 User Manual on CD for more information on parameters.