V. alarms – Grain Systems PNEG-526 User Manual
Page 23

17
Tower Dryer Operations & Service
V. Alarms
The controller checks the sensors and control status regularly. If abnormal
conditions are detected, a corresponding alarm will go off, an alarm message will come up
on the main screen and the dryer will be shut down.
ALARM
CAUSES
SOLUTION
Moisture out of range -
the moisture coming out
of the dryer was 2.5%
above or below the set-
point for more than one
hour under AUTO control
mode
• Sensor box plugged and
sensor was not covered
by grain
• Dry sensor out of
calibration
• Too big swing of
moisture coming into the
dryer
• Clear the sampler and
sensor box
• Calibrate the sensor
• Run the dryer manually
for one pass
Dry sensor error -
sensor reading is less than
6% or higher than 40%
• Bad wiring
• Bad sensor
• Bad circuit board
• Check connection
• Change the sensor
• Change the circuit board
Dry grain temperature out
of range (0-300F)
• Bad wiring
• Bad sensor
• Bad circuit board
• Check connection
• Change the sensor
• Change the circuit board
Wet sensor error -
sensor readng is less than
6% or higher than 40%
• Bad wiring
• Bad sensor
• Bad circuit board
• Check connection
• Change the sensor
• Change the circuit board
Wet grain temp. out of
range
(0-300F)
• Bad wiring
• Bad sensor
• Bad circuit board
• Check connection
• Change the sensor
• Change the circuit board
Column grain temperature
RTD out of range
(0-300F)
• Bad wiring
• Bad sensor
• Bad circuit board
• Check connection
• Change the sensor
• Change the circuit board
TRI-POINT MOISTURE CONTROLLER
23