beautypg.com

VEGA VEGACOM 557 Profibus FMS User Manual

Page 9

background image

VEGACOM 557 Profibus FMS

9

Product description

PROFIBUS interface

Standards conformity

to DIN 19 245, part 1 and part 2
to pr EN 50 170
acc. to ISO 7498

Interface standard

RS 485

Network topology

linear bus (active bus terminator on both
ends), stubs are possible

Number of stations per segment
- without repeater

1)

32 stations

- with repeater

up to 127 stations

Max. bus length
- without repeater

100 m with 12 Mbits/s

- cable A

200 m with 1500 Kbits/s up to 1.2 km with
93.75 Kbits/s

- cable B

200 m with 500 Kbits/s up to 1.2 km with
93.75 Kbits/s

- with repeater

up to the 10 km range

Connection cable

2-wire screened

2)

, twisted

Transmission

half-duplex, serially asynchronous, slip resistant
synchronisation

Transmission rate

3)

9.6; 19.2; 93.75 kbits/s up to 1.2 km
187.5 kbits/s up to 600 m
500 kbits/s up to 200 m

Coding system

NRZ code

Number of bits

11 Bits: 1 start bit, 8 data bits, 1 parity bit,
1 stop bit

Parity

EVEN

Data backup

LRC

Electrical protective measures

Protection:
not mounted

IP 00

in carrier BGT 596
or BGT LOG 571
- front side completely equipped

IP 40

- upper and lower side

IP 00, BGT LOG 571 IP 20

- wiring side

IP 00

in housing type 505
- front side

IP 40

- other sides

IP 30

Protection class

II (in housing type 505)

Overvoltage category

II

Electrical protective measures

Reliable separation acc. to VDE 0106,

between power supply, LOGBUS,

part 1

DISBUS, PC and PROFIBUS connection

- reference voltage

250 V

- test voltage

3 kV

1)

Repeater = line amplifier (possibly are at least 3, partly up to 10)

2 )

Depending on the ambient conditions (EMC), screening can be deleted

3)

Adjustable via DIL switch on the component