VEGACOM 557 Profibus FMS

Setup

Transmission of the data base to CP

Menu: Load –> CP data base transfer –> FD-CP

If the CP parameter setting is finished, the data base must be transferred to the communica-
tion processor:
- provide connection PC/programming device with CP5431
- stop CP with "Load –> CP Stop"
- transfer parameter data base to the CP: Load –> CP data base transfer –> FD-CP
- set CP to operating condition with "Load –> CP Start"

Important:
The new data base is only active after switching off the voltage supply of the CP (mains com-
ponent) and switching it on again.

4.4 S5 functional components for data exchange between AG and CP

To ensure the data exchange between the S5 application (AG) and the communication proc-
essor (CP), the AG is equipped with integrated functional components (FB). These are de-
scribed in detail in the Siemens automation manual and are only explained briefly here. With
this FB, orders are transferred to the CP and data received from the CP are collected.

A description of the necessary integrated functional components follows. Each FB requires an
interface and an order number as parameter which was determined with the CP parameter
setting (see: FMS planning).

Parameters

SSNR

Interface number

A-NR

Order number

ANZW

Indication word

DBNR

Data component number

QANF / ZANF Relative initial address within the type
QLAE / ZLAE Number of source/destination data
PAFE

Parameter setting error

BLGR

Block size

Indication word ANZW

The indication word consists of 3 groups

Bit

7

6

5

4

3

2

1

0

Meaning

free

Error message

Data administr.

Status administr.

Status administration:
Bit 0: Handshake useful
Bit 1: Order running
Bit 2: Order ready without error
Bit 3: Order ready with error, cause of error is stated in the error message