beautypg.com

Basic properties of profibus fms and profibus dp, Protocol architecture – VEGA VEGACOM 557 Profibus FMS User Manual

Page 45

background image

VEGACOM 557 Profibus FMS

45

Supplement

Basic properties of Profibus FMS and
Profibus DP

PROFIBUS determines the technical and
functional properties of a series field bus
system, through which distributed, digital
field automation instruments in the lower (sen-
sor/actuator level) up to the medium (cell
level) power range can be connected.
PROFIBUS distinguishes between Master
and Slave instruments.

Master instruments

determine the data

traffic on the bus. A master can send mes-
sages without external request, provided the
master is authorised for bus access. In the
Profibus protocol, masters are also called
active participants.

Slave instruments

are low-expenditure

peripherals. Typical slave instruments are
sensors, actuators, transmitters. They do not
receive authorisation for bus access, i.e. they
are only allowed to acknowledge received
messages or transmit messages to a master
on its request. Slaves are also called passive
participants. They require only a small portion
of the bus protocol, and as a result, a very
low-expenditure implementation of the bus
protocol is ensured.

Protocol architecture

PROFIBUS is based on a number of ap-
proved international and national standards.
The protocol architecture orients itself on OSI
(Open System Interconnection) multilayer
system, according to the international stand-
ard ISO 7498. The architecture of the
Profibus FMS and the Profibus DP protocol is
shown in figure 2.

PROFIBUS layer 1 (Physical Layer)

The application range of a field bus system is
mainly determined by the selection of the
transmission medium and the physical bus
interface. Beside the demands on the trans-
mission reliability, the expenditures for pro-
curement and installation of the bus cable are
of great consequence. That’s why the
Profibus standard makes provision for differ-
ent versions of transmission technology, while
keeping to a single, uniform bus protocol.

PROFIBUS layer 2 (Data Link Layer)

The second layer of the OSI multilayer sys-
tem realises the functions of the bus access
control and data backup, as well as the man-
aging of transmission protocols and tel-
egrams. Layer 2 is called Fieldbus Data Link
(FDL) with PROFIBUS.

Protocol architecture

Profibus DP

Profibus FMS

Application process

DIN (E)

User-Interface

PNO

Application Layer Interface (ALI)

19 245

Profile

part 3

Direct-Data-Link-Mapper (DDLM)

DIN

Application-Layer (7)

19 245

Fieldbus Message Specification (FMS)

Layer 3 to 7

part 2

Lower Layer Interface (LLI)

is not defined

Layer 3 to 6

is not defined

Subset of

Data-Link-Layer (2)

DIN

Data-Link-Layer (2)

DIN 19 245

Fieldbus Data Link (FDL)

19 245

Fieldbus Data Link (FDL)

part 1

Physical-Layer (1)

part 1

Physical-Layer (1)

Profibus transmission medium