Fb244: send component – VEGA VEGACOM 557 Profibus FMS User Manual
Page 29

VEGACOM 557 Profibus FMS
29
Setup
Dat administration:
Bit 4: Data acceptance running
Bit 5: Data transfer being effected
Bit 6: Data acceptance being effected
Bit 7: Disable data block
Failure message:
0: No failure
1: Wrong type information in the functional component
2: Storage area not available
3: Storage area too small
4: Delayed acknowledgement
5: Failure in the indication word
6: Invalid source/destination parameters
A: Connection error
B: Handshake error
C:System error
D:Blocked data block
E: Order cannot be processed
F: Connection or ANR not specified
FB244: SEND component
This functional component gives a transmission command to the CP. The CP initiates the
PROFIBUS FMS Read service to read out the measured values
FB244: SEND
Parameter
Format
Description
Example
SSNR
KY
Interface number
KY 0,0
A-NR
KY
Order number
KY 0,1
ANZW
MW
Indication value
MW 2
QTYP
KC
Source type: Data component
KC DB
DBNR
KY
Data component number
KY 0,240
QANF / ZANF
KY
Relative initial address within the type
KY +20
QLAE / ZLAE
KF
Number of source/destination data
KF +15
PAFE
MB
Parameter setting error
MB 255
In the example, an order is given to the CP. The order block describes the CP order and can
be found in the data component DB240 from data word DW20 with a length of 15 data words.
The parameters ANZW and PAFE deliver status and failure information for processing (here
MW2 or MB 255).