DB240: Basic settings

In this DB, the basic settings and order blocks for CP5431 are determined. Here, only the
Start-target DB (data word 0) may be modified. All other parameters may not be modified.

Start-target DB:
- By this, when using FB210 (read in all measured values) the first data component for saving

the measured values can be stated. Since 16 measured value blocks are read in, 16 data
components must be reserved by the Start-target DB.

DB240 C:[email protected] LAE=40 /64

Blatt 1

—— basic adjustment ——

0: KY = 000,220; Start-target DB (meas. value: DB 220-235)*

1: KY = 000,015; Start-target DB (meas. value: DB 220-235)*

2: KH = 1000; Start Index for 1. meas. value block

3: KY = 000,000; reserved

4: KC =’V-RE’; — READ-corder, Sub Index—

6: KF = +00100; Time out

7: KH = 0000; reserved

8: KC =’DB’; destination, identification

9: KY = 000,220; destination DB

10: KF = +00000; Offset

11: KC =’AR’; Data type Array

12: KF = +00016;

13: KC =’OS’;

14: KF = +00006;

15: KC =’VF’;

16: KY = 003,004; ID=3, Len=4; Index with Subindex

17: KF = +04096; variable Index

18: KY = 000,001; Subindex

19: KY = 000,000; —Read-order without SubIndex—

20: KC =’V-RE’; — Read order without SubIndex —

22: KF = +00100; Time out

23: KH = 0000; reserved

24: KC =’DB’; destination, identification

25: KY = 000,220; destination DB

26: KF = +00000; destination Offset

27: KC =’AR’; Data type Array

28: KF = +00016;

29: KC =’OS’; type of element, Octett-String

30: KF = +00006;

31: KC =’VF’;

32: KY = 002,002; ID=2, Len=2: Index without SubIndex

33: KF = +04096; Index

34: KY = 000,000; ———————————————

35: