Fb211: read in measured value blocks – VEGA VEGACOM 557 Profibus FMS User Manual
Page 38

38
VEGACOM 557 Profibus FMS
Setup
FB 210 C:[email protected] LAE=93
Page 2
0076 QANF : KF +20
0078 QLAE : KF +15
007A PAFE : MB 255
007C :
007E :
0080 :
0082 :
0084 :
0086 :
0088 :
008A :
008C :
008E :
0090 :
0092 REC :O M 0.0
0094 :ON M 0.0
0096 :SPA FB 245 — RECEIVE_ALL order ——
0098 Name :RECEIVE
009A SSNR : KY 0,0
009C A-NR : KY 0,0 Order no.=0 –> RECEIVE_ALL
009E ANZW : MW 2
00A0 ZTYP : KC NN
00A2 DBNR : KY 0,0
00A4 ZANF : KF +0
00A6 ZLAE : KF +0
00A8 PAFE : MB 255
00AA :
00AC :
00AE :BE
MW 10 = MW_BLKNO Meas. value block number
FB211: Read in measured value blocks
With this functional component, a measured value block (16 measured values) is read in.
Important information:
The interface number and the order number must be adapted to your application if necessary.
These values relate to the values set in the CP connection planning.
Call:
The functional component must be called up in each program cycle.
:SPA FB 211
Name :R-MW-BLK
BLCK : MW 30
meas. value block number = 1..16
DB : MW 32
data component for file
STAT : MW 50
Status
Status :
0000
= OK
0080 = BLCK Error, unvalid block number
00FF = no reading order given to CP