Configuration Properties (cont.)

CP Name

Type

NV Num.

R/W

Applies To

Range

Default Value

Description

cpAllCurrent

SCPTminSndT

4

R/W

All current output

network variables

0 - 1 hour,

49 minutes,

13 seconds,

500ms (6553.5

seconds)

15 seconds

Throttle for all current output network

variables. After propagation of a network

variable, updates to the same network

variable are blocked for the time set by this

configuration property. The configuration

property is shared, but each current output

network variable has its own independent

throttle counter that resets to the value

specified by this CP after it has been

propagated.

cpAllPowerFactor

SCPTminSndT

5

R/W

All power factor

network variables

0 - 1 hour,

49 minutes,

13 seconds,

500ms (6553.5

seconds)

15 seconds

Throttle for all power factor output network

variables. After propagation of a network

variable, updates to the same network

variable are blocked for the time set by this

configuration property. The configuration

property is shared, but each power factor

output network variable has its own

independent throttle counter that resets to

the value specified by this CP after it has been

propagated.

cpFrequency

SCPTminSndT

28

R/W

nvoFrequency

0 - 1 hour,

49 minutes,

13 seconds,

500ms (6553.5

seconds)

15 seconds

Throttle for nvoFrequency. After propagation,

updates to the network variable are blocked

for the time set by this configuration property.

cpAlert

SCPTmaxSendTime

22

R/W

nvoAlert

0 - 6553.4

seconds (0-

65534 raw)

900 seconds (9000

raw)

Heartbeat for nvoAlert. If the network variable

has not changed after the time interval

specified here (and therefore has not been

propagated), the value will be propagated and

the heartbeat counter restarted.

cpStartupCount

SCPTmaxSendTime

10

R/W

nvoStartupCount

0 - 6553.4

seconds (0-

65534 raw)

900 seconds (9000

raw)

Heartbeat for nvoStartupCount. If the

network variable has not changed after the

time interval specified here (and therefore

has not been propagated), the value will

be propagated and the heartbeat counter

restarted.

cpEnrgyResetCnt

SCPTmaxSendTime

11

R/W

nvoEnrgyResetCnt

0 - 6553.4

seconds (0-

65534 raw)

900 seconds (9000

raw)

Heartbeat for nvoEnrgyResetCnt. If the

network variable has not changed after the

time interval specified here (and therefore

has not been propagated), the value will

be propagated and the heartbeat counter

restarted.

cpPulseCount

SCPTsndDelta

0

R/W

nvoPulseCount1,

nvoPulseCount2

0 -4294967295

counts

0 (send any

change)

Number of counts that nvoPulseCount1 or

nvoPulseCount2 must change by to cause

propagation of the respective network

variable.