Installation Guide
Power Monitoring
E50F2A, E50F5A
TM
Configuration Properties (cont.)
CP Name
Type
NV Num.
R/W
Applies To
Range
Default Value
Description
cpAllCurrent
SCPTminSndT
4
R/W
All current output
network variables
0 - 1 hour,
49 minutes,
13 seconds,
500ms (6553.5
seconds)
15 seconds
Throttle for all current output network
variables. After propagation of a network
variable, updates to the same network
variable are blocked for the time set by this
configuration property. The configuration
property is shared, but each current output
network variable has its own independent
throttle counter that resets to the value
specified by this CP after it has been
propagated.
cpAllPowerFactor
SCPTminSndT
5
R/W
All power factor
network variables
0 - 1 hour,
49 minutes,
13 seconds,
500ms (6553.5
seconds)
15 seconds
Throttle for all power factor output network
variables. After propagation of a network
variable, updates to the same network
variable are blocked for the time set by this
configuration property. The configuration
property is shared, but each power factor
output network variable has its own
independent throttle counter that resets to
the value specified by this CP after it has been
propagated.
cpFrequency
SCPTminSndT
28
R/W
nvoFrequency
0 - 1 hour,
49 minutes,
13 seconds,
500ms (6553.5
seconds)
15 seconds
Throttle for nvoFrequency. After propagation,
updates to the network variable are blocked
for the time set by this configuration property.
cpAlert
SCPTmaxSendTime
22
R/W
nvoAlert
0 - 6553.4
seconds (0-
65534 raw)
900 seconds (9000
raw)
Heartbeat for nvoAlert. If the network variable
has not changed after the time interval
specified here (and therefore has not been
propagated), the value will be propagated and
the heartbeat counter restarted.
cpStartupCount
SCPTmaxSendTime
10
R/W
nvoStartupCount
0 - 6553.4
seconds (0-
65534 raw)
900 seconds (9000
raw)
Heartbeat for nvoStartupCount. If the
network variable has not changed after the
time interval specified here (and therefore
has not been propagated), the value will
be propagated and the heartbeat counter
restarted.
cpEnrgyResetCnt
SCPTmaxSendTime
11
R/W
nvoEnrgyResetCnt
0 - 6553.4
seconds (0-
65534 raw)
900 seconds (9000
raw)
Heartbeat for nvoEnrgyResetCnt. If the
network variable has not changed after the
time interval specified here (and therefore
has not been propagated), the value will
be propagated and the heartbeat counter
restarted.
cpPulseCount
SCPTsndDelta
0
R/W
nvoPulseCount1,
nvoPulseCount2
0 -4294967295
counts
0 (send any
change)
Number of counts that nvoPulseCount1 or
nvoPulseCount2 must change by to cause
propagation of the respective network
variable.