Operation — sequence, Boiler manual – Weil-McLain GOLD CGS 550-110-260/02002 User Manual

Page 31

background image

Part number 550-110-260/0200

31

Boiler Manual

Operation —

sequence

9a

Figure 18

Control module sequence of operation — status light indications

1.

Read Lighting instructions

on page 34. This

information is also located on a label on the inside
of the boiler jacket door panel.

2.

Raise

room thermostat to call for heat.

3.

Inducer and circulator energize.

After pressure

switch proves proper airflow, control module
initiates 30-second prepurge.

4.

Control module sparks

the pilot and opens pilot

valve in main gas valve.

a. If pilot

does not

light within 15 seconds, pilot

valve is closed and spark generator is turned
off. Control module initiates a 15-second
postpurge, then starts a new cycle.

b. If pilot

does

light and control module senses

flame current, spark generator is turned off and
main valve opens.

5. During

main burner operation

:

a. Control module monitors pilot flame current.

If signal is lost

, main valve closes, spark

generator activates and sequence returns to
step

4

.

b.

If power is interrupted

, control system

shuts

off

pilot and main gas valves and restarts at step

1

when power is restored.

6. In the event the

limit control shuts down the

boiler

— The control module closes the pilot and

main gas valves, but keeps the inducer operating
for 15-second postpurge.
— The circulator continues to operate.

7.

Lower

room thermostat setting to stop call for heat.

Thermostat is satisfied — Pilot and main gas valves
are closed — Inducer operates for 15-second
postpurge — Circulator is shut off.

8. Boiler is now in the

off cycle

.

9.

Repeat

steps

1

through

6

several times to verify

operation.

10.

Return

the thermostat to normal setting.

11. Set thermostat heat anticipator setting to 0.4 amps,

adjusted for gas valve and control current.

1.

Standby

Waiting for call for heat

·

2.

Call for heat

·

Circulator on

·

Blower on

3.

Limit circuit

·

Limit controls closed

·

Block switch contacts closed

4.

Pressure circuit

·

Pressure switch contacts closed

·

Prepurge for 30 seconds

5.

Pilot flame proven *

·

Gas valve open

·

Pilot remains on

·

Boiler producing heat

6.

Limit cycle

·

Limit circuit open

·

Gas valve closed

7.

Flame outage *

·

Flame out

·

Boiler recycles

8.

Thermostat satisfied

·

Circulator off

·

Blower postpurge

9.

Circulator exercise routine

·

Circulator turns on for 30 seconds
if boiler not operated for 30 days

* If pilot flame is not proven in 15 seconds, control module will flash the FLAME light, but will continue indefinitely with attempts to light the pilot burner.

The control module will not lockout on a failure to establish flame. It will lockout if line voltage polarity is reversed, stray voltage is sensed on thermostat
line, pressure switch sticks closed or fails to make within 5 minutes or if flame is sensed when it shouldn’t be there. The boiler will reset after these lockouts
if any of the following occurs:

• 1 hour waiting period • Opening and closing of thermostat circuit • Removal of 120 VAC power for at least 45 seconds.

POWER

TSTAT

CIRC

LIMIT

PRESS

SWITCH

FLAME

Call for

heat?

Timing

or

= "ON"

= "OFF"

NO

NO

NO

YES

YES

YES

YES

YES

YES

35 sec

15 sec

15 sec

30 sec

Steps

(Following step 8, cycle goes back to step 1.)

26030