Water piping — low temp systems, Gold cgs gas-fired water boiler, Valve adjustment – Weil-McLain GOLD CGS 550-110-260/02002 User Manual
Page 18
Part number 550-110-260/0200
18
GOLD
CGs
Gas-Fired Water Boiler
1. Set the valves while the system is cool, setting for the coldest expected water temperature
(usually 60 °F since the system will often drop to room temperature between cycles).
2. Start with valve
7a
fully closed and
7b
fully open.
3. Gradually open valve
7a
while closing valve
7b
until the temperature at gauge
8
reads
130 °F when gauge
4a
reads 60 °F.
4. Note that valve
7a
regulates the amount of hot water from the boiler supply which mixes
with return water. Valve
7b
regulates the amount of system water flowing through the
boiler secondary loop.
Valve adjustment
(Figure 12 and 13 only)
Water piping —
low temp systems
3d
Primary/secondary
bypass piping is preferred because the flow rate and temperature drop in
the heating circuit(s) is determined only by the heating circuit circulator(s). So adjustment
of the bypass valves in the boiler circuit will not cause a change in the heating circuit rate and
temperature distribution.
Figures 8
and
9
show suggested bypass arrangements using
primary/secondary
bypass piping
(preferred) for low temperature systems such as
radiant heating systems
or
converted gravity
systems
. For alternatives, see pages 20 through 23.
The bypass valves (items
7a
and
7b
) provide mixing of hot boiler outlet water with cooler
system return water — set to assure a minimum return water temperature (at least 130 °F) to
the boiler. Set the valves as explained below.
Primary/secondary
(preferred) bypass
piping method
Temperature gauges
Gauge
4a
is suggested, but optional on any system.
Gauge
4b
is optional on converted gravity systems, but
required
on radiant heating systems
— to display the water temperature being supplied to the radiant tubing.
Gauge
8
is
required
on all systems to assure the return water temperature is accurately set for
a minimum of 130 °F. If this gauge is not available however, adjust the valves such that the
boiler-mounted temperature/pressure gauge reads at least 150 °F when the system return
water is cold (approximately 60 °F water temperature).
Failure to
prevent low return water temperature
to the boiler could cause corrosion of
the boiler sections or burners, resulting in severe personal injury, death or substantial property
damage.
Radiant heating system piping should include a means of
regulating the boiler return
water temperature
and the
system supply temperature
(such as provided by an
injection
pumping control
).
Boiler return water temperature will be adequately controlled using the methods shown in
this manual provided the
system supply temperature is relatively constant
.
DO NOT
apply the methods of this manual if the system is equipped with an
outdoor
reset control
. Instead,
provide controls and piping
which can
regulate the boiler return
water temperature at no less than 130 °F
regardless of system supply temperature. Contact
your Weil-McLain representative for suggested piping and control methods.
Failure to
prevent cold return water temperature
to the boiler could cause corrosion
damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.