beautypg.com

Water piping — low temp systems, Gold cgs gas-fired water boiler, Valve adjustment – Weil-McLain GOLD CGS 550-110-260/02002 User Manual

Page 18

background image

Part number 550-110-260/0200

18

GOLD

CGs

Gas-Fired Water Boiler

1. Set the valves while the system is cool, setting for the coldest expected water temperature

(usually 60 °F since the system will often drop to room temperature between cycles).

2. Start with valve

7a

fully closed and

7b

fully open.

3. Gradually open valve

7a

while closing valve

7b

until the temperature at gauge

8

reads

130 °F when gauge

4a

reads 60 °F.

4. Note that valve

7a

regulates the amount of hot water from the boiler supply which mixes

with return water. Valve

7b

regulates the amount of system water flowing through the

boiler secondary loop.

Valve adjustment

(Figure 12 and 13 only)

Water piping —

low temp systems

3d

Primary/secondary

bypass piping is preferred because the flow rate and temperature drop in

the heating circuit(s) is determined only by the heating circuit circulator(s). So adjustment
of the bypass valves in the boiler circuit will not cause a change in the heating circuit rate and
temperature distribution.

Figures 8

and

9

show suggested bypass arrangements using

primary/secondary

bypass piping

(preferred) for low temperature systems such as

radiant heating systems

or

converted gravity

systems

. For alternatives, see pages 20 through 23.

The bypass valves (items

7a

and

7b

) provide mixing of hot boiler outlet water with cooler

system return water — set to assure a minimum return water temperature (at least 130 °F) to
the boiler. Set the valves as explained below.

Primary/secondary

(preferred) bypass

piping method

Temperature gauges

Gauge

4a

is suggested, but optional on any system.

Gauge

4b

is optional on converted gravity systems, but

required

on radiant heating systems

— to display the water temperature being supplied to the radiant tubing.

Gauge

8

is

required

on all systems to assure the return water temperature is accurately set for

a minimum of 130 °F. If this gauge is not available however, adjust the valves such that the
boiler-mounted temperature/pressure gauge reads at least 150 °F when the system return
water is cold (approximately 60 °F water temperature).

Failure to

prevent low return water temperature

to the boiler could cause corrosion of

the boiler sections or burners, resulting in severe personal injury, death or substantial property
damage.

Radiant heating system piping should include a means of

regulating the boiler return

water temperature

and the

system supply temperature

(such as provided by an

injection

pumping control

).

Boiler return water temperature will be adequately controlled using the methods shown in
this manual provided the

system supply temperature is relatively constant

.

DO NOT

apply the methods of this manual if the system is equipped with an

outdoor

reset control

. Instead,

provide controls and piping

which can

regulate the boiler return

water temperature at no less than 130 °F

regardless of system supply temperature. Contact

your Weil-McLain representative for suggested piping and control methods.

Failure to

prevent cold return water temperature

to the boiler could cause corrosion

damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.