beautypg.com

Water piping — low temp systems, Gold cgs gas-fired water boiler, Boiler-bypass piping method temperature gauges – Weil-McLain GOLD CGS 550-110-260/02002 User Manual

Page 20: Valve adjustment

background image

Part number 550-110-260/0200

20

GOLD

CGs

Gas-Fired Water Boiler

Water piping —

low temp systems

3e

This piping method is called a

boiler-bypass

because part of the circulator flow is bypassed

around the boiler (through valve

7a

). This method reduces the flow rate throughout the

boiler, in order to raise the average water temperature in the boiler enough to prevent flue gas
condensation. Boiler-bypass piping is effective for some boilers — including the CGs —
provided the flow rates are adjusted according to the instructions following.

Figures 10

and

11

are alternative piping suggestions for

converted gravity

(large water content

or steam systems) or

radiant heating system

— for use when primary/secondary piping

can’t be applied. (

Figure 12

is another alternative, using system bypass in place of boiler-

bypass piping.

Figure 12

however, is not suitable for radiant heating applications because it

does not protect the radiant system from possible high water temperature.)

Boiler-bypass piping keeps system flow rate as high as possible and temperature drop as low
as possible, helping to equalize the building heat distribution.

Boiler-bypass piping

method

Temperature gauges

Gauge

4a

is optional if the bypass valves will be adjusted using cold (or room temperature)

return water to the boiler. (When setting the valves without gauge

4a

installed — using cold

or room temperature water — assume the return water temperature to be 60 °F. Set the valves
so gauge

8

reads at least 120 °F.

Gauge

4b

is optional on converted gravity systems, but

required

on radiant heating systems

— to display the water temperature being supplied to the radiant tubing.

Gauge

8

is

required

on all systems to assure reliable adjustment of the bypass valves. The

boiler-mounted temperature/pressure gauge can be used if a separate temperature gauge is
not installed.

1. Start with valve

7a

fully closed and

7b

fully open.

2. Gradually open valve

7a

while closing valve

7b

until the temperature at gauge

8

reads

60 °F higher than gauge

4a

. A minimum 60 °F temperature rise through the boiler assures

a low enough flow rate and high enough average temperature to prevent condensation
even with low system return water temperature.

3. Valve

7a

regulates the system flow rate, while valve

7b

regulates the boiler flow rate.

4. The boiler-mounted temperature/pressure gauge may be used in place of a separate

gauge

8

.

Valve adjustment

Failure to

prevent low return water temperature

to the boiler could cause corrosion of

the boiler sections or burners, resulting in severe personal injury, death or substantial property
damage.

Radiant heating system piping should include a means of

regulating the boiler return

water temperature

and the

system supply temperature

(such as provided by an

injection

pumping control

).

Boiler return water temperature will be adequately controlled using the methods shown in
this manual provided the

system supply temperature

is

relatively constant

.

DO NOT

apply the methods of this manual if the system is equipped with an

outdoor

reset control

. Instead,

provide controls and piping

which can

regulate the boiler return

water temperature

at

no less than 130 °F

regardless of system supply temperature. Contact

your Weil-McLain representative for suggested piping and control methods.

Failure to

prevent cold return water temperature

to the boiler could cause corrosion

damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.