Water piping — low temp systems, Gold cgs gas-fired water boiler, Boiler-bypass piping method temperature gauges – Weil-McLain GOLD CGS 550-110-260/02002 User Manual
Page 20: Valve adjustment
Part number 550-110-260/0200
20
GOLD
CGs
Gas-Fired Water Boiler
Water piping —
low temp systems
3e
This piping method is called a
boiler-bypass
because part of the circulator flow is bypassed
around the boiler (through valve
7a
). This method reduces the flow rate throughout the
boiler, in order to raise the average water temperature in the boiler enough to prevent flue gas
condensation. Boiler-bypass piping is effective for some boilers — including the CGs —
provided the flow rates are adjusted according to the instructions following.
Figures 10
and
11
are alternative piping suggestions for
converted gravity
(large water content
or steam systems) or
radiant heating system
— for use when primary/secondary piping
can’t be applied. (
Figure 12
is another alternative, using system bypass in place of boiler-
bypass piping.
Figure 12
however, is not suitable for radiant heating applications because it
does not protect the radiant system from possible high water temperature.)
Boiler-bypass piping keeps system flow rate as high as possible and temperature drop as low
as possible, helping to equalize the building heat distribution.
Boiler-bypass piping
method
Temperature gauges
Gauge
4a
is optional if the bypass valves will be adjusted using cold (or room temperature)
return water to the boiler. (When setting the valves without gauge
4a
installed — using cold
or room temperature water — assume the return water temperature to be 60 °F. Set the valves
so gauge
8
reads at least 120 °F.
Gauge
4b
is optional on converted gravity systems, but
required
on radiant heating systems
— to display the water temperature being supplied to the radiant tubing.
Gauge
8
is
required
on all systems to assure reliable adjustment of the bypass valves. The
boiler-mounted temperature/pressure gauge can be used if a separate temperature gauge is
not installed.
1. Start with valve
7a
fully closed and
7b
fully open.
2. Gradually open valve
7a
while closing valve
7b
until the temperature at gauge
8
reads
60 °F higher than gauge
4a
. A minimum 60 °F temperature rise through the boiler assures
a low enough flow rate and high enough average temperature to prevent condensation
even with low system return water temperature.
3. Valve
7a
regulates the system flow rate, while valve
7b
regulates the boiler flow rate.
4. The boiler-mounted temperature/pressure gauge may be used in place of a separate
gauge
8
.
Valve adjustment
Failure to
prevent low return water temperature
to the boiler could cause corrosion of
the boiler sections or burners, resulting in severe personal injury, death or substantial property
damage.
Radiant heating system piping should include a means of
regulating the boiler return
water temperature
and the
system supply temperature
(such as provided by an
injection
pumping control
).
Boiler return water temperature will be adequately controlled using the methods shown in
this manual provided the
system supply temperature
is
relatively constant
.
DO NOT
apply the methods of this manual if the system is equipped with an
outdoor
reset control
. Instead,
provide controls and piping
which can
regulate the boiler return
water temperature
at
no less than 130 °F
regardless of system supply temperature. Contact
your Weil-McLain representative for suggested piping and control methods.
Failure to
prevent cold return water temperature
to the boiler could cause corrosion
damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.