Water piping —

single-zone system

3b

Expansion tank

Diaphragm-type or bladder-type
expansion tank — Figure 4

1. Ensure expansion tank size will handle boiler and

system water volume and temperature. Tank must
be located in boiler return piping as close to boiler
as possible, before inlet side of circulator. See tank
manufacturer’s instructions for details.

2. Install an

automatic air vent

in air vent tapping as

shown.

Figure 4

Diaphragm- or bladder-type expansion tank

Piping to single-zone system using
diaphragm-type or bladder-type expansion
tank. See Table 3 for piping sizes.

Figure 5

Closed-type expansion tank

Piping to single-zone system using closed-
type expansion tank. See Table 3 for piping
sizes.

Closed-type expansion tank —
Figure 5

1. Ensure expansion tank size will handle boiler and

system water volume and temperature. See tank
manufacturer’s instructions for details.

2. Connect tank to ½" NPT tapping located behind

supply outlet, using ½" NPT piping. Pitch any
horizontal piping up towards tank 1 inch per 5 feet
of piping.

Use

Figure 4

or

Figure 5

only for single-zone systems designed for return water at least 130 °F.

For systems with low return water temperature possible, such as converted gravity systems
and radiant heating systems, refer to the special piping suggestions of pages 18-23. Failure to
prevent low return water temperature to the boiler could cause corrosion of the boiler sections
or burners, resulting in severe personal injury, death or substantial property damage.

26010

From
system

Cold
water
fill

To DIAPHRAGM
expansion tank
and fittings

Isolation
valve

Isolation
valve

To system

Circulator*

Circulator

Drain
valve

Relief
valve

Automatic
air vent

*Alternate

location

26011

To system

From
system

Isolation
valve

Drain
valve

Relief
valve

Circulator*

Isolation
valve

Circulator

Cold water fill

CLOSED-type
expansion tank

*Alternate

location

Undersized expansion tanks cause system water to be lost from relief valve and makeup water
to be added through fill valve. Eventual section failure can result.