Boiler manual – Weil-McLain GOLD CGS 550-110-260/02002 User Manual

Page 11

background image

Part number 550-110-260/0200

11

Boiler Manual

Figure 3

Sizing air openings for CGs installations

Outside

Outside or ventilated attic

Ventilated

crawl space

Or

CGs

12”

Max

Duct

Air from

or

Lower Opening in Floor
or Vertical Duct

Outside

Attic

D

Air

opening

Air

opening

Outside

Inside

CGs

12”

Max

12”

Max

Duct

Duct

Air from
Through horizontal
ducts

Outside

C

Air

opening

Air

opening

12”

Max

12”

Max

Outside

CGs

Air
from

Directly

Outside

B

Air

opening

Air

opening

12”

Max

12”

Max

Outside

Inside

CGs

Air from Inside

A

Other

appliances

CGs

CGs

Direct exhaust vent installation

(CGs using room air for combustion)

Room Air Openings

Exception to
combustion air
opening rules:

Direct vent installation

(combustion air piped to CGs)

Room

with other appliances

shared

Room

with other appliances

shared

CGs

in room

alone

CGs

in room

alone

CGs

Combustion

air piping

Other

appliances

CGs

Combustion

air piping

Required area of the air openings given in this
table are free area — after the correction for
louver obstruction. (See

below.)

Exception

Apply this table only to installations with
clearances no smaller than those shown in
Figure 1, page 7 of this manual.

For installations with clearances less than
shown in Figure 1, page 7 of this manual,
provide 2 openings, each with 1 square inch
of free area per 1,000 Btuh of total input of
all appliances.

2 Openings —
each opening:

2 Openings —
each opening:

2 Openings —
each opening:

2 Openings —
each opening:

2 Openings —
each opening:

2 Openings —
each opening:

2 Openings —
each opening:

2 Openings —
each opening:

2 Openings —
each opening:

2 Openings —
each opening:

2 Openings —
each opening:

2 Openings —
each opening:

NO Openings are
needed, provided:

NO
NO LESS

Building must not be of Tight construction

Example:

combustion air openings are needed when the boiler (and other appliances) are installed in a space with a volume

than 50 cubic feet per 1,000 Btuh of all installed appliances. Sum the total input of all appliances in MBH

(1,000's of Btuh) and multiply this number times 50.

(see page 10).

For total input of 100 MBH (100,000 Btuh), minimum volume is 50 x 100 = 5,000 cubic feet. At a ceiling

height of 8 feet, space must have at least 5,000 ÷ 8 = 625 square feet (25 feet x 25 feet, for instance).

NO Openings are
needed, provided:

NO Openings are
needed, provided:

NO Openings are
needed, provided:

Clearance around
boiler is
than shown in
Figure 1, page 7
of this manual.

NO LESS

Clearance around
boiler is
than shown in
Figure 1, page 7
of this manual.

NO LESS

Clearance around
boiler is
than shown in
Figure 1, page 7
of this manual.

NO LESS

Clearance around
boiler is
than shown in
Figure 1, page 7
of this manual.

NO LESS

1 square inch

free area per

1 square inch

free area per

1 square inch

free area per

1 square inch

free area per

1 square inch

free area per

1 square inch

free area per

1 square inch

free area per

1 square inch

free area per

1 square inch

free area per

1 square inch

free area per

1 square inch

free area per

1 square inch

free area per

1,000

plus CGs

Btuh input of

other appliances

4,000

plus CGs

Btuh input of

other appliances

2,000

plus CGs

Btuh input of

other appliances

4,000

plus CGs

Btuh input of

other appliances

1,000

CGs

Btuh input of

other appliances
only (not

)

4,000

CGs

Btuh input of

other appliances
only (not

)

2,000

CGs

Btuh input of

other appliances
only (not

)

4,000

CGs

Btuh input of

other appliances
only (not

)

4,000

CGs

Btuh input

of

4,000

CGs

Btuh input

of

4,000

CGs

Btuh input

of

4,000

CGs

Btuh input

of

26007