Start-up — operate boiler, Start-up — if boiler doesn’t start, Boiler manual – Weil-McLain GOLD CGS 550-110-260/02002 User Manual

Page 29: Continued, Check burner flames, Check for

background image

Part number 550-110-260/0200

29

Boiler Manual

4.

Check around the boiler

for gas odor following

the procedure of section

7a

of this manual.

Start-up —

operate boiler

continued

7b

Figure 16

Typical pilot burner flame

Figure 17

Typical main burner flame

Check burner flames

View pilot and main flames through the inspection port
in the Air inlet box front cover.

Pilot burner flame

Proper

pilot flame characteristics (see

Figure 16

):

1. Blue flame.
2. Inner cone engulfing pilot flame sensor.
3. Pilot flame sensor glowing cherry red.

Improper

pilot flame characteristics:

1. Overfired — Large flame lifting or blowing past

pilot flame sensor.

2. Underfired — Small flame. Inner cone not engulfing

pilot flame sensor.

3. Lack of primary air — Yellow flame tip.
4. Incorrectly heated pilot flame sensor.

Main burner flame

Proper

main burner flame characteristics

(see

Figure 17

):

1. Yellow-orange streaks may appear (caused by dust).

Improper

main burner flame characteristics:

1. Overfired — Large flames.
2. Underfired — Small flames.
3. Lack of primary air — Yellow tipping on flames

(sooting will occur).

Start-up —

if boiler doesn’t start . . .

7c

Check for:

1. Loose connections, blown fuse or service switch

off?

2. High limit switch set below boiler water

temperature?

3. Thermostat set below room temperature?

4. Gas not turned on at meter or boiler?

5. Incoming gas pressure less than:

5" w.c. for natural gas?

11" w.c. for propane gas?

If none of the above corrects the problem, refer to

Troubleshooting

, section

11

of this manual.

26023

Spark
electrode

Inner

cone

Pilot
flame
sensor

26024

Transparent

blue flame

Inner flame

If you discover evidence of any gas leak, shut down
the boiler at once. Find the leak source with bubble
test and repair immediately. Do not start boiler again
until corrected. Failure to comply could result in severe
personal injury, death or substantial property damage.