Field wiring, Gold cgs gas-fired water boiler, Wiring connections – Weil-McLain GOLD CGS 550-110-260/02002 User Manual

Page 26: Electrical installation must comply with, Thermostat, Junction box (furnished)

background image

Part number 550-110-260/0200

26

GOLD

CGs

Gas-Fired Water Boiler

Figure 15

Field wiring connections —

service switch and thermostat

(or end switch) provided by

installer

For your safety,

turn off electrical

power supply at service entrance
panel before making any electrical
connections

to avoid possible

electric shock hazard. Failure to do
so can cause severe personal injury
or death.

Field wiring

6

1. National Electrical Code and

any other national, state,
provincial or local codes or
regulations.

2. In Canada, CSA C22.1

Canadian Electrical Code Part 1,
and any local codes.

Field wiring

F

actory wiring

Service

switch

(not provided)

Junction box,

boiler left side

T h e r m o s t a t
leads, through
jacket left side

Service

switch

(not provided)

Thermostat

or end switch

(not provided)

Thermostat

or end switch

(not provided)

Black

White

Green

Ground screw

Wire nuts

Black

Black

120 VAC
Hot

Neutral

Ground

26021

The CGs control module is
polarity-sensitive. The hot and
neutral wires must be connected to
the correct leads. A flashing

POWER

light usually indicates reversed
polarity of 120 VAC lead wires.

Thermostat

1. Connect thermostat as shown on wiring diagram

on boiler.

2.

Install on inside wall away from influences of
drafts, hot or cold water pipes, lighting fixtures,
television, sunrays, or fireplaces.

3. If thermostat has a heat anticipator, set heat

anticipator in thermostat to match power
requirements of equipment connected to it. If
connected directly to boiler, set for 0.4 amps. For
other devices, refer to manufacturer’s specifications.
Wiring diagram on boiler gives setting for control
module and gas valve. Also see instructions with
thermostat.

Junction Box (furnished)

1. Connect 120 VAC power wiring as shown in

Figure 15.

2. Fused disconnect or service switch (15 amp.

recommended) may be mounted on this box. For
those installations with local codes which prohibit
installation of fused disconnect or service switch
on boiler, install a 2 x 4 cover plate on the boiler
junction box and mount the service switch
remotely as required by the code.

Wiring connections

Boiler is shipped with controls completely wired.

Electrical installation

must comply with:

Wiring must be N.E.C. Class 1.

If original wiring as supplied with
boiler must be replaced, use only
type

105 °C

wire or equivalent.

Boiler must be

electrically

grounded

as required by National

Electrical Code ANSI/NFPA 70 –
latest edition.