System-bypass (alternate) piping, Water piping — refrigeration system, Boiler manual – Weil-McLain GOLD CGS 550-110-260/02002 User Manual

Page 23: For converted gravity (or steam) systems, Prevent chilled water from entering boiler

background image

Part number 550-110-260/0200

23

Boiler Manual

3

System or zone circulator

7

System temperature valves (see instructions to the left for
adjusting valves)

8

Blend temperature gauge

9

Relief valve

10

Automatic air vent (with diaphragm-type expansion
tank), or connect to tank fitting (closed-type expansion
tank). DO NOT use an automatic air vent when using
closed-type expansion tank. It would allow air to leave
the system, causing waterlogging of the expansion tank.

11

Fill valve

12

Diaphragm-type or bladder-type expansion tank, if used
(For closed-type expansion tank, pipe from top of air
separator to tank fitting as in Figure 5.)

system-bypass (alternate) piping —

for converted gravity (or steam) systems

Figure 12

System-bypass piping

Zoning with zone valve or circulators, return
water 130 °F or higher.

(Alternative to boiler-bypass piping
Figures 10

and 11)

Figure 13

Piping refrigeration systems

Prevent chilled water from
entering boiler

Water piping —

refrigeration system

3g

26018

10

Cold

water

fill

11

12

9

8

7a

7b

Alternate
circulator
location

To system

From system

26019

Water
chiller

Expansion tank

Circulator

Check
valve

Strainer

Boiler

Shut-off
valve

System
supply

System
return

Balancing
valve

MODEL

CGs

Install boiler so that chilled
medium is piped in parallel with
the heating boiler. Use appropriate
valves to prevent chilled medium
from entering boiler. See

Figure 13

for typical installation of balancing
valve and check valve.

If boiler is connected to heating
coils located in air handling units
where they can be exposed to
refrigerated air, use flow control
valves or other automatic means to
prevent gravity circulation during
cooling cycle.

3f