beautypg.com

Water piping — general information, Gold cgs gas-fired water boiler, General piping information – Weil-McLain GOLD CGS 550-110-260/02002 User Manual

Page 14: Relief valve, System water piping, Pressure/temperature gauge, Circulator

background image

Part number 550-110-260/0200

14

GOLD

CGs

Gas-Fired Water Boiler

Water piping —

general information

3a

General piping information

If installation is to comply with ASME or Canadian requirements, an
additional

high temperature limit

is needed. Install control in supply

piping between boiler and isolation valve. Set second control to minimum
20 °F above setpoint of first control. Maximum allowable setpoint is 240 °F.
See section

9b

, page 32 for wiring.

A

low water cutoff device

is required when boiler is installed above

radiation level or by certain state or local codes or insurance companies.
Use low water cutoff designed for water installations. Electrode probe-
type is recommended. Purchase and install in tee in supply piping above
boiler.

Use

backflow check valve

in cold water supply as required by local codes.

Relief valve

Install relief valve vertically in ¾" tapping on side of boiler. See

Figure 4

or 5

and the tag attached to the relief valve for manufacturer’s instructions.

To avoid water damage or scalding due to relief valve
operation:

Discharge line must be connected to relief valve outlet and

run to a

safe place of disposal

. Terminate the discharge line to eliminate

possibility of severe burns should the valve discharge.

Discharge line must be as short as possible and be the

same size as

the valve discharge connection

throughout its entire length.

Discharge line must

pitch downward

from the valve and terminate at

least 6" above the floor drain where any discharge will be clearly visible.

The discharge line shall

terminate plain, not threaded,

with a material

serviceable for temperatures of 375 °F or greater.

Do not pipe the discharge to any place where freezing could occur.

No shutoff valve

shall be installed between the relief valve and boiler,

or in the discharge line. Do not plug or place any obstruction in the
discharge line.

Failure to comply

with the above guidelines could result in failure of

the relief valve to operate, resulting in possibility of severe personal
injury, death or substantial property damage.

Test the operation of the valve

after filling and pressurizing system

by lifting the lever. Make sure the valve discharges freely. If the valve
fails to operate correctly, replace it with a new relief valve.

System water piping

See

Figure 4

(diaphragm-type or bladder-type

expansion tank) or

Figure 5

(closed-type expansion

tank) on page 15, and

Table 3

below, for near-boiler

and single-zone systems designed for return water at
least 130 °F.

See pages 16-17 to complete multiple-zone piping or
pages 18-23 to complete piping for radiant heating
systems or converted gravity systems.

Refer to page 23 for boilers used with refrigeration systems.

Install boiler such that —

Chilled medium, if used, is piped in parallel with
heating boiler. Use appropriate valves to prevent
chilled medium from entering boiler. Consult
I=B=R Installation and Piping Guides.

If boiler is connected to heating coils located in air
handling units where they can be exposed to
refrigerated air, use flow control valves or other
automatic means to prevent gravity circulation
during cooling cycle. Circulation of cold water
through the boiler could result in damage to the
heat exchanger, causing possible severe personal
injury, death or substantial property damage.

Pressure/temperature gauge

Install pressure/temperature gauge in tee on supply piping (as shown in
drawing on page 3). The gauge well is a self-closing valve, allowing removal
of the gauge without draining the system.

Slowly remove pressure/temperature gauge from well.
The self-closing valve could leak if clogged with
sediment. If water begins to spray, stop removing gauge.
Close system fill valve and drain enough water to release
system pressure before continuing with gauge removal.
Escaping hot water could cause severe personal injury.

Circulator

The circulator is shipped loose (wiring pre-attached
to boiler) to allow you to locate it either in the return
or supply piping, as desired. See page 3 for a typical
installation. Pipe the expansion tank to the suction side
of the circulator whenever possible. Install an air
separator in the supply piping. Connect the expansion
tank to the air separator only if the separator is on the
suction side of the circulator. Always install the system
fill connection at the same point as the expansion tank
connection to the system.

Figures 4

and

5

show typical

near-boiler piping connections.

Table 3

Water pipe size (based on 20 °F rise)

Boiler

model

number

To

system

From

system

CGs-3

1"

1"

CGs-4

1"

1"

CGs-5

1"

1"

CGs-6

1 ¼"

1 ¼"

Note: Circulator flange supplied with boiler is same size as

recommended piping above.