beautypg.com

Start-up — preparation, Fill the system with water, Check for gas leaks – Weil-McLain GOLD CGS 550-110-260/02002 User Manual

Page 27

background image

Part number 550-110-260/0200

27

Boiler Manual

Determine if water treatment is needed

Do not use

petroleum-based cleaning or sealing

compounds

in boiler system. Severe damage to boiler

will occur, resulting in substantial property damage.

Eliminate all system leaks. Continual fresh makeup
water will reduce boiler life. Minerals can build up in
sections, reducing heat transfer, overheating cast iron,
and causing section failure.

Start-up —

preparation

7a

Fill the system with water

1. Close manual and automatic

air vents

and boiler

drain cock.

2.

Fill to correct system pressure

. Correct pressure

will vary with each application. Typical cold water
fill pressure for a residential system is 12 psi.

3.

Purge air

from system:

a. Connect a hose to the purge valve (see drain

valves, item

6

, in suggested piping diagrams

on pages 17 through 21,

Figure 6

through

Figure 11

). Route hose to an area where water

can drain and be seen.

b. Close the boiler or system isolation valve

between the purge valve and fill connection to
the system.

c. Close zone isolation valves.

d. Open quick-fill valve on cold water makeup

line.

e. Open purge valve.

f.

One zone at a time, open the isolation valves.
Allow water to run through the zone, pushing
out the air. Run until no noticeable air flow is
present. Close the zone isolation valves and
proceed with the next zone. Follow this
procedure until all zones are purged.

g. Close the quick-fill water valve and purge valve

and remove the hose. Open all isolation valves.
Watch that system pressure rises to correct
cold-fill pressure.

h. After the system has operated for a while,

eliminate any residual air by using the manual
air vents located throughout the system.

i.

If purge valves are not installed in system, open
manual air vents in system one at a time,
beginning with lowest floor. Close vent when
water squirts out. Repeat with remaining vents.

4. Open

automatic air vent

(diaphragm-type or

bladder-type expansion tank systems only) one
turn.

5. Open other vents:

a. Starting on the lowest floor, open air vents one

at a time until water squirts out.

b. Repeat with remaining vents.

6. Refill to correct pressure.

Verify water chemistry

Consult local water treatment companies for unusually
hard water areas (above 7 grains hardness) or low pH
water conditions (below 7.0). Boiler water pH of 7.0
to 8.5 is recommended.

Freeze protection (when used)

Use antifreeze made especially for hydronic systems.
Inhibited propylene glycol is recommended.

Do not use

ethylene glycol,

automotive or undiluted
antifreeze

. Severe personal injury

or death can result.

1. Determine

antifreeze quantity

according to system

water content. Boiler water content is listed on
page 59. Remember to include expansion tank water
content.

2. Follow antifreeze manufacturer's instructions.
3. A 50% solution of propylene glycol/water provides

maximum protection to about -30 °F.

4. Local codes may require

back flow preventer

or

actual disconnect from city water supply.

5. When using antifreeze in a system with automatic

fill, install a water meter to monitor water makeup.
Glycol will leak before the water begins to leak,
causing glycol level to drop. Added water will dilute
the antifreeze, reducing the freeze protection level.

Check for gas leaks

Before starting the boiler, and during initial operation,
smell near the floor and around the boiler for gas
odorant or any unusual odor. Do not proceed with
start-up if there is any indication of a gas leak. Repair
any leak at once.

Propane boilers only — Your propane supplier mixes
an odorant with the propane to make its presence
detectable. In some instances, the odorant can fade, and
the gas may no longer have an odor. Before start-up
(and periodically thereafter), have the propane supplier
verify the correct odorant level in the gas.