Table 4

Pipe capacity for 0.60 specific gravity natural gas

Gas piping

continued

5

Natural Gas:

1. Refer to

Table 4

for pipe length and diameter. Base

on rated boiler input (divide by 1,000 to obtain
cubic feet per hour).

Table 4

is only for gas with

specific gravity 0.60, with a pressure drop
through the gas piping of 0.30" w.c.

For additional

gas pipe sizing information, refer to ANSI Z223.1
(or B149.1 or B149.2 for Canadian installations).

2. Inlet pressure required at gas valve inlet:

• Maximum: 13" w.c.
• Minimum: 5" w.c.
• Manifold gas pressure: 3.5" w.c.

3. Install 100% lockup gas pressure regulator in

supply line

if inlet pressure exceeds 13" w.c.

Adjust for 13" w.c. maximum.

Propane Gas:

1. Contact gas supplier to size pipes, tanks and 100%

lockup gas pressure regulator.

2. Adjust propane supply regulator provided by gas

supplier for 13" w.c. maximum pressure.

3. Inlet pressure required at gas valve inlet:

• Maximum: 13" w.c.
• Minimum: 11" w.c.
• Manifold gas pressure: 10" w.c.

Do not check for gas leaks with
an open flame

— use bubble test.

Failure to use bubble test or check
for gas leaks can cause severe
personal injury, death or substantial
property damage.

2.

Support piping

with hangers, not by boiler or its

accessories.

3.

Purge all air

from gas supply piping.

4. Before placing boiler in operation,

check boiler

and its gas connection for leaks.

a.

Close manual main shutoff

valve during any

pressure testing at less than 13" w.c.

b.

Disconnect boiler and gas valve from gas
supply piping

during any pressure testing

greater than 13" w.c.

5.

Use pipe dope compatible with propane gases.

Apply sparingly only to male threads of pipe joints
so that pipe dope does not block gas flow.

Failure to apply pipe dope

as

detailed above can result in severe
personal injury, death or substantial
property damage.

Gas pipe

length

(feet)

Capacity of pipe for pipe size of:

(Capacity in cubic feet gas per hour)

½"

¾"

1"

1¼"

1½"

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

860

40

63

130

245

500

760

50

56

115

215

440

670

75

45

93

175

360

545

100

38

79

150

305

460

150

31

64

120

250

380